Inspection Detail

Case Status: CLOSED

Inspection: 419164.015 - Omar Electric, Inc.

Inspection Information - Office: Chicago North Area Office

 

Inspection Nr: 419164.015
Report ID: 0524200
Date Opened: 05/07/2012

Site Address:
Omar Electric, Inc.
11130 King Street
Franklin Park, IL 60131

Mailing Address:
9712 Franklin Ave., Franklin Park, IL 60131

Union Status: NonUnion

SIC:

NAICS: 238210/Electrical Contractors


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/09/2012

Emphasis:

Case Closed: 12/05/2012


Related Activity
Type Activity Nr Safety Health
Referral 339280 Yes
Inspection 426091 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 7 7
Current Violations 7 7
Initial Penalty $19,600 $0 $0 $0 $0 $19,600
Current Penalty $11,700 $0 $0 $0 $0 $11,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100332 B01 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  
2. 01002A Serious 19100333 A01 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  
3. 01002B Serious 19100333 A02 07/09/2012 10/15/2012 $0 $0 $0 I - Informal Settlement  
4. 01003 Serious 19100333 B02 I 07/09/2012 10/15/2012 $1,620 $2,800 $0 I - Informal Settlement  
5. 01004 Serious 19100335 A01 I 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  
6. 01005 Serious 19100335 A01 V 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  
7. 01006 Serious 19100335 A01 IV 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  
8. 01007 Serious 19100335 A02 II 07/09/2012 10/15/2012 $1,680 $2,800 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 16015.015
Event: 05/04/2012
Employee Is Struck By Electric Arc Flash And Receives Multip

At approximately 10:45 a.m. on May 4, 2012, Employee #1 was running draw wire (also known as fish tape) through conduit piping on a 480V panel while it was energized. He placed heavy cardboard over the bus bars to prevent contact and was not wearing any proper personal protective equipment. As he pushed the draw wire through, it sprung back and came in contact with the bus bars causing an electric arc flash that struck Employee #1. Employee #1 sustained multiple burns over his body. A duffel bag containing fire resistant rated clothing and a face shield was not brought to the job site. Employee #1 was transported to a medical center, where he received burn treatment and was then hospitalized.

Keywords: Burn, Elec Circ Part--Misc, Electric Arc, Electrical Box, Electrical Work, Lockout/Tagout, PPE, Struck Against

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 419164.015 45 M Hospitalized injury Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close