Inspection: 1155266.015 - Noel Alvarado-Perez

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 1155266.015
Report ID: 0626300
Date Opened: 06/15/2016

Site Address:
Noel Alvarado-Perez
307 West Moore Avenue
Terrell, TX 75160

Mailing Address:
826 Poinsettia Drive, Lancaster, TX 75146

Union Status: NonUnion

SIC:

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Fat/Cat

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/15/2016

Emphasis: L:Constr6

Case Closed: 03/06/2024


Related Activity
Type Activity Nr Safety Health
Accident 1102048
Inspection 1161934 Yes
Case Status: CLOSED
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $15,143 $0 $0 $0 $0 $15,143
Current Penalty $7,680 $0 $0 $0 $0 $7,680
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A01 11/09/2016 $6,240 $12,471 $0 I - Informal Settlement  
2. 01001B Serious 19261203 A 11/09/2016 11/22/2016 $0 $0 $0 I - Informal Settlement  
3. 01002 Serious 19260501 B04 I 11/09/2016 11/22/2016 $1,440 $2,672 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 86049.015
Event: 06/14/2016
Employee electrocuted while installing HVAC equipment

At 11:50 a.m. on June 14, 2016 an employee and a co-worker were installing air conditioning equipment in an attic. Prior to the incident, the employee had installed plywood decking on the ceiling joists to serve as a base for installing the AC equipment in the attic crawl space of a building. The employee and the coworker had also placed two large components of the AC equipment in the attic. An electrical conduit terminating at a junction box was located inside the attic. The junction box, which provided power to a light bulb located in the middle of a back office area, contained a lock nut that was not installed on the strain relief coupling of the metal conduit. A sharp edge of the loose coupling came in contact with the wires, which resulted in compromised wires causing the junction box and metal conduit to become energized. Prior to entering the attic, the power to the electrical conduit running through the attic crawl space had not been turned off. As the employee and coworker entered the space to install the AC equipment, the employee was electrocuted when he came into contact with the energized conduit.

Keywords: Air Conditioner, Attic, Conduit, Electrical, Electrocuted

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 1155266.015 42 M Fatality Heating, air conditioning, and refrig. mechanics
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.