10544279209/03/198717110R. J. R. Mechanical, Inc.

Abstract: AN ELECTRICIAN HAD REPLACED THE ATTACHMENT PLUG FOR THE POWER SUPPLY CORD ON A MILLER DIAL ARC 250 AC/DC WELDER. THE CORD CONTAINED ONLY THREE CONDUCTORS: ONE BLUE AND ONE ORANGE CONDUCTOR, WHICH HE CONNECTED TO THE TWO CURRENT CARRYING PINS ON THE PLUG, AND ONE "BARE" ONE, WHICH HE CONNECTED TO THE GROUNDING PIN. SHORTLY, AFTER THE REPAIR, A WELDER TURNED ON THE WELDING MACHINE TO PERFORM SOME WORK. WHEN THE WELDER ATTEMPTED TO ATTACH THE GROUND LEAD, HE RECEIVED AN ELECTRIC SHOCK. HE CALLED THE ELECTRICIAN TO TURN THE MACHINE OFF. THE ELECTRICIAN WAS ELECTROCUTED WHEN HE CONTACTED THE FRAME OF THE WELDING MACHINE. AN INSPECTION OF THE INTERNAL WIRING OF THE WELDING MACHINE SHOWED THAT THE ORANGE CONDUCTOR WAS CONNECTED TO THE CHASSIS OF THE MACHINE AND THAT THE BLUE AND "BLACK" CONDUCTORS WERE THE CURRENT CARRYING CONDUCTORS. THUS, THE ELECTRICIAN HAD CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR DIRECTLY TO AN ENERGIZED LINE.

Keywords: ELECTRICAL, E GI VII, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTROCUTED

Employee Details
Employee # Inspection Nr Age Sex Degree of Injury Nature of Injury Occupation
1 105442784 Fatality Electric Shock Electricians
2 105442792 Occupation Not Listed

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.