Inspection Detail
Inspection: 105442792 - R. J. R. Mechanical, Inc.
Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation
Site Address:
R. J. R. Mechanical, Inc.
Jackson St.
Barnwell, SC 29812
Mailing Address:
P. O. Box 435, Sta. B), Spartanburg, SC 29812
Union Status: NonUnion
SIC:1711
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/17/1987
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 02/08/1988
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360280234 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Other | 19260404 F06 | 10/13/1987 | 10/16/1987 | $0 | $0 | $0 | 11/02/1987 | F - Formal Settlement | |
| 2. | 01001B | Other | 19260404 A01 | 10/13/1987 | 10/16/1987 | $0 | $0 | $0 | 11/02/1987 | F - Formal Settlement |
Investigation Summary
AN ELECTRICIAN HAD REPLACED THE ATTACHMENT PLUG FOR THE POWER SUPPLY CORD ON A MILLER DIAL ARC 250 AC/DC WELDER. THE CORD CONTAINED ONLY THREE CONDUCTORS: ONE BLUE AND ONE ORANGE CONDUCTOR, WHICH HE CONNECTED TO THE TWO CURRENT CARRYING PINS ON THE PLUG, AND ONE "BARE" ONE, WHICH HE CONNECTED TO THE GROUNDING PIN. SHORTLY, AFTER THE REPAIR, A WELDER TURNED ON THE WELDING MACHINE TO PERFORM SOME WORK. WHEN THE WELDER ATTEMPTED TO ATTACH THE GROUND LEAD, HE RECEIVED AN ELECTRIC SHOCK. HE CALLED THE ELECTRICIAN TO TURN THE MACHINE OFF. THE ELECTRICIAN WAS ELECTROCUTED WHEN HE CONTACTED THE FRAME OF THE WELDING MACHINE. AN INSPECTION OF THE INTERNAL WIRING OF THE WELDING MACHINE SHOWED THAT THE ORANGE CONDUCTOR WAS CONNECTED TO THE CHASSIS OF THE MACHINE AND THAT THE BLUE AND "BLACK" CONDUCTORS WERE THE CURRENT CARRYING CONDUCTORS. THUS, THE ELECTRICIAN HAD CONNECTED THE EQUIPMENT GROUNDING CONDUCTOR DIRECTLY TO AN ENERGIZED LINE.
Keywords: ELECTRICAL, E GI VII, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING, ELECTROCUTED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 105442792 | Occupation Not Listed |
Translate