- Part Number:1926
- Part Number Title:Safety and Health Regulations for Construction
- Subpart:1926 Subpart CC
- Subpart Title:Cranes and Derricks in Construction
- Standard Number:
- Title:Power line safety (up to 350 kV)--equipment operations.
- GPO Source:
Devices originally designed by the manufacturer for use as: A safety device (see § 1926.1415), operational aid, or a means to prevent power line contact or electrocution, when used to comply with this section, must meet the manufacturer's procedures for use and conditions of use.
Voltage (nominal, kV, alternating current) |
Minimum clearance distance (feet) |
up to 50 over 50 to 200 over 200 to 350 over 350 to 500 over 500 to 750 over 750 to 1,000 over 1,000 |
15 20 25 35 45 |
Note: The value that follows "to" is up to and includes that value. For example, over 50 to 200 means up to and including 200kV.
[75 FR 48142, August 9, 2010]