- Part Number:1926
- Part Number Title:Safety and Health Regulations for Construction
- Subpart:1926 Subpart CC
- Subpart Title:Cranes and Derricks in Construction
- Standard Number:
- Title:Power line safety (up to 350 kV)--equipment operations.
- GPO Source:
Devices originally designed by the manufacturer for use as: A safety device (see § 1926.1415), operational aid, or a means to prevent power line contact or electrocution, when used to comply with this section, must meet the manufacturer's procedures for use and conditions of use.
| Voltage (nominal, kV, alternating current) |
Minimum clearance distance (feet) |
| up to 50 over 50 to 200 over 200 to 350 over 350 to 500 over 500 to 750 over 750 to 1,000 over 1,000 |
15 20 25 35 45 |
Note: The value that follows "to" is up to and includes that value. For example, over 50 to 200 means up to and including 200kV.
[75 FR 48142, August 9, 2010]