Powered by GoogleTranslate

Inspection Detail

Inspection: 974832 - Silverstone Electric Company

Inspection Information - Office: Hartford Area Office

 

Inspection Nr: 974832
Report ID: 0112000
Date Opened: 12/26/1985

Site Address:
Silverstone Electric Company
510 Barnum Avenue
Bridgeport, CT 06608

Mailing Address:
, , 00000

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/13/1986

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 10/15/1986


Related Activity
Type Activity Nr Safety Health
Accident 360665954
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations
Initial Penalty $250 $0 $0 $0 $0 $250
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100305 A01 I 02/20/1986 03/21/1986 $250 $250 $0 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 14278162
Event: 12/23/1985
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC MOTOR

AN EMPLOYEE OF AN ELECTRICAL CONTRACTING COMPANY WAS WORKING IN THE CEILING PLENUM OF AN OFFICE AT A COMMUNITY COLLEGE TO REPLACE DEFECTIVE WIRING TO A MOTOR. HE TEMPORARILY CONNECTED THE NEW CONDUCTORS IN A JUNCTION BOX BUT DID NOT CONNECT THE FLEXIBLE METAL CONDUIT SERVING AS THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT. HE CLOSED A DISCONNECT SWITCH TO ENERGIZE THE MOTOR AND RECEIVED A FATAL ELECTRIC SHOCK. FROZEN TO THE CIRCUIT, HIS BODY WAS RELEASED ONLY WHEN THE POWER TO THE DISCONNECT SWITCH WAS SHUT OFF. THE NEXT DAY, AN ELECTRICIAN TESTED THE DUCT ON WHICH THE MOTOR WAS SITTING AND FOUND IT TO BE ENERGIZED. ONE OF THE CIRCUIT CONDUCTORS OF THE MOTOR (PEERLESS, 1/6 HORSEPOWER, 1150 RPM, MODEL P-12, SERIAL NUMBER 906389) HAD FAULTED TO THE MOTOR HOUSING, WHICH WAS SITTING ON THE DUCT.

Keywords: ELECTRIC MOTOR, ELECTRICAL, E GI VII, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 974832 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.