Powered by GoogleTranslate

Inspection Detail

Inspection: 850313 - Bruce Oakley Inc

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 850313
Report ID: 0627100
Date Opened: 10/26/1984

Site Address:
Bruce Oakley Inc
3700 Lincoln Ave
North Little Rock, AR 72114

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5153

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/30/1984

Emphasis: N:Grain

Case Closed: 11/27/1984


Related Activity
Type Activity Nr Safety Health
Accident 360550925
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $960 $0 $480 $0 $0 $1,440
Current Penalty $960 $0 $480 $0 $0 $1,440
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 11/09/1984 11/12/1984 $480 $480 $0 -  
2. 01002 Serious 19100304 F05 II 11/09/1984 11/12/1984 $480 $480 $0 -  
3. 02001 Repeat 19100303 G02 II 11/09/1984 11/12/1984 $480 $480 $0 -  

Investigation Summary

Investigation Nr: 14495964
Event: 10/25/1984
ELECTRIC SHOCK - CORROSION-CAUSED FAULT IN SWITCH

A 4-FOOT-BY-8-FOOT ROOM IN A SALT GRINDING BAY HOUSED SWITCHES ALONG ONE WALL. A 5-FOOT SECTION OF METAL CABLE TRAY HAD BEEN MOUNTED THERE; AND, ON TOP OF THE CABLE TRAY, A MAIN SWITCH HAD BEEN INSTALLED WITH A SHORT METAL NIPPLE. THREE OTHER SWITCHES WERE ALSO INSTALLED ON TOP OF THE TRAY IN THE SAME MANNER. ALL OF THE SWITCHES WERE RATED 480 VOLTS, 3 PHASE. BECAUSE OF CORROSION PROBLEMS, THE SWITCHES WERE SUPPLIED BY CONDUCTORS RUN IN NONMETALLIC CONDUIT. HOWEVER, THE SWITCHES WERE OF THE GENERAL-PURPOSE TYPE, AND CORROSION HAD CAUSED LEAKAGE TO DEVELOP FROM THE CENTER PHASE TO THE SWITCH HANDLE. AN EMPLOYEE MOVED THE HANDLE OF THE MAIN SWITCH IN THE UP POSITION. BECAUSE THE METAL TRAY WAS NOT GROUNDED, THIS ENERGIZED THE METAL CABLE TRAY AND THE OTHER THREE SWITCHES. THE EMPLOYEE WAS ELECTROCUTED AS HE TOUCHED ONE OF THE SMALLER SWITCHES.

Keywords: ELECTRICAL, ELECTRIC SWITCH, E GI VII, ELECTROCUTED, CURRENT LEAKAGE, CORROSION, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 850313 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.