Powered by GoogleTranslate

Inspection Detail

Inspection: 835199 - B.V.F. Construction Company

Inspection Information - Office: Osha Philadelphia Area Office

 

Inspection Nr: 835199
Report ID: 0317000
Date Opened: 08/05/1987

Site Address:
B.V.F. Construction Company
1335-37 Pine Street
Philadelphia, PA 19107

Mailing Address:
78 Tomlinson Road, Suite C, Huntingdon Valley, PA 19006

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/05/1987

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 11/19/1987


Related Activity
Type Activity Nr Safety Health
Accident 360113609
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $1,120 $0 $0 $0 $0 $1,120
Current Penalty $1,120 $0 $0 $0 $0 $1,120
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260020 B01 11/05/1987 11/12/1987 $560 $560 $0 -  
2. 01001B Serious 19260020 B02 11/05/1987 11/12/1987 $0 $0 $0 -  
3. 01001C Serious 19260021 B02 11/05/1987 11/12/1987 $0 $0 $0 -  
4. 01002A Serious 19260403 B01 11/05/1987 11/12/1987 $560 $560 $0 -  
5. 01002B Serious 19260404 F06 11/05/1987 11/12/1987 $0 $0 $0 -  
6. 02001 Other 19030002 A01 11/05/1987 11/08/1987 $0 $0 $0 -  
7. 02002 Other 19040008 11/05/1987 11/12/1987 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14314421
Event: 07/30/1987
ELECTRIC SHOCK - GROUND FAULT IN METAL FRAME

An employee was using an extension cord that had no equipment grounding conductor. The conductors in the extension cord were exposed at several places on the cord. One of the exposed conductors was touching the metal portion of a scaffold. The metal portion of the scaffold was touching a metal stud frame, energizing it. When a second employee, an apprentice carpenter, drove a stud into the frame, he was electrocuted.

Keywords: E GI V, ELEC INSULATION, ELECTRICAL, CORD SET, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 835199 Fatality Electric Shock Carpenter apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close