Powered by GoogleTranslate

Inspection Detail

Inspection: 317144459 - Par Electrical Contractors Inc

Inspection Information - Office: Santa Ana District Office

 

Inspection Nr: 317144459
Report ID: 0950631
Date Opened: 03/24/2014

Site Address:
Par Electrical Contractors Inc
El Toro & Normandale
Lake Forest, CA 92630

Mailing Address:
525 Corporate Dr., Escondido, CA 92029

Union Status: Union

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/21/2014

Emphasis:

Case Closed: 05/22/2015


Related Activity
Type Activity Nr Safety Health
Accident 102857083
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $450 $0 $450
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2811 08/28/2014 09/02/2014 $0 $450 $0 09/04/2014 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202558094
Event: 03/19/2014
Two Workers Are Burned in Electric Arc Flash

On March 19, 2014, Employees #1 and #2, electrical power installers/repairers employed by PAR Electrical Contractors, Inc., were working as part of a crew installing a power transmission line. They were working on a new above-ground primary cabinet (PME). The crew was "cutting over" the new "A" phase load to the new PME #6058 and verifying that they were energizing the proper new "A" phase cable and that it was properly terminated, tagged, and mapped. They were "phoning out" the conductor by connecting a battery-operated walkie-talkie device to each end of the selected cable and verifying verbally with the persons at each end that they were connected through the same cable. This was necessary because workers at the two ends were not in view of one another. The crew first opened the down circuit structure (#B5143734) and identified the new cable. They then proceeded to set up the tools and equipment to connect the phone there. Employees #1 and #2 proceeded to the PME #6058 to connect to the opposite end of the "A" phase cable to phone back to the circuit side. Employee #1 opened the PME, which was locked and secured with star screws, and reached for the cable marked "A" phase. He removed it from the stand-off bushing and attached the phone to the probe. Employee #2 was standing behind Employee #1. Employee #1 connected one lead wire from the phone to ground. When he tried to place the second lead from the phone, a phase-to-ground fault occurred through the phone he was holding in his hand. Both Employee #1 and Employee #2 were burned in the resulting electric arc flash. Emergency services were called, and the Orange County Fire Authority responded. The two employees were transported to Western Medical Center, admitted, and treated for second and third degree burns to the face and arms. Both required surgery for their burns. Both the Orange County Fire Authority and the employer reported this event to Cal/OSHA on March 19, 2014. The subsequent investigation determined that the workers had inadvertently opened the line side of the cabinet, which was energized, rather than the load side of the cabinet.

Keywords: BURN, ELECTRIC ARC, INSTALLING, ELECTRIC CABLE, ELECTRICIAN, CONSTRUCTION, ELEC UTILITY WORK, ELECTRICAL CABINET, ARM, FACE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 317144459 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
2 317144459 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.