Inspection Detail
Inspection: 317143824 - Cam Contractors Inc
Inspection Information - Office: Santa Ana District Office
Site Address:
Cam Contractors Inc
16282 Tisburi Circle
Huntington Beach, CA 92649
Mailing Address:
Po Box 711659, Santee, CA 92702
Union Status: Union
SIC:1623
NAICS: 237130/Power and Communication Line and Related Structures Construction
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/25/2014
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 10/06/2022
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 102851128 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 7 | 2 | 9 | |||
Current Violations | 7 | 2 | 9 | |||
Initial Penalty | $96,575 | $0 | $0 | $1,235 | $0 | $97,810 |
Current Penalty | $96,575 | $0 | $0 | $1,235 | $0 | $97,810 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 2943 B01 | 03/28/2014 | 04/02/2014 | $900 | $900 | $0 | 04/23/2014 | F - Formal Settlement | |
2. | 01002 | Other | 3276 E11 | 03/28/2014 | 04/02/2014 | $335 | $335 | $0 | 04/23/2014 | F - Formal Settlement | |
3. | 02001 | Serious | 2940 B | 03/28/2014 | 04/02/2014 | $8,100 | $8,100 | $0 | 04/23/2014 | F - Formal Settlement | |
4. | 03001 | Serious | 2940 C | 03/28/2014 | 04/02/2014 | $10,125 | $10,125 | $0 | 04/23/2014 | F - Formal Settlement | |
5. | 04001 | Serious | 2940 D | 03/28/2014 | 04/02/2014 | $8,100 | $8,100 | $0 | 04/23/2014 | F - Formal Settlement | |
6. | 05001 | Serious | 29400001 A | 03/28/2014 | 04/02/2014 | $10,125 | $10,125 | $0 | 04/23/2014 | F - Formal Settlement | |
7. | 06001 | Serious | 2943 F01 | 03/28/2014 | 04/02/2014 | $25,000 | $25,000 | $0 | 04/23/2014 | F - Formal Settlement | |
8. | 07001 | Serious | 2943 G01 | 03/28/2014 | 04/02/2014 | $25,000 | $25,000 | $0 | 04/23/2014 | F - Formal Settlement | |
9. | 08001 | Serious | 3203 A04 | 03/28/2014 | 04/02/2014 | $10,125 | $10,125 | $0 | 04/23/2014 | F - Formal Settlement |
Investigation Summary
At approximately 12:16 p.m. on September 30, 2013, Employee #1, a 28-year-old male Electricians' Apprentice with Cam Contractors Inc., was working inside of an underground electrical vault, at a residential properly in Huntington Beach, California. Employee #1 was performing Cable In Conduit (CIC) testing on high voltage (12kV) equipment and conductors. The CIC testing required Employee #1 to inspect and test the de-energized elbows connected to a Buried Underground Residential Distribution (BURD) switch identified as BS2P0885. The unit was a submersible load break, oil switch module manufactured by Kuhlman, bearing Serial No. 3006100290. During the scheduled outage, two of the six elbows on the BURD switch remained energized. The underground vault was constructed of concrete walls and concrete foundation. The entrance to the vault was a 24-inch diameter opening located in a public road. During the CIC testing, Employee #1 contacted a position on the BURD switch that was energized and carrying 12kV of alternating current and was electrocuted. CAM Contractors, Inc. was a medium-sized electrical contractor that specialized in high voltage electric power line construction. Employee #1 was employed full-time as an apprentice lineman that worked for the Employer since July 26, 2013.
Keywords: SHOCK, ELECTRICAL VAULT, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, UNDRGRD INSTALLATION, ELEC CIRC PART--MISC, UNDRGRD POWER LINE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 317143824 | Fatality | Electric Shock | Electricians' apprentices |