Inspection Detail
Inspection: 317008480 - D & D Maintenance Services Inc
Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation
Site Address:
D & D Maintenance Services Inc
13 Sabina Court
Hanahan, SC 29406
Mailing Address:
4754 Franchise Street, North Charleston, SC 29418
Union Status: NonUnion
SIC:7699
NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/16/2014
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 04/25/2014
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102668183 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 1 | 4 | |||
| Current Violations | 2 | 1 | 3 | |||
| Initial Penalty | $4,375 | $0 | $0 | $750 | $0 | $5,125 |
| Current Penalty | $1,875 | $0 | $0 | $0 | $0 | $1,875 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100147 C01 | 01/21/2014 | 02/24/2014 | $375 | $375 | $0 | - | ||
| 2. | 01002 | Serious | 19100333 A | 01/21/2014 | 02/24/2014 | $2,000 | $2,000 | $0 | A - Amendment | Citation has been deleted. | |
| 3. | 01003 | Serious | 19100335 A01I | 01/21/2014 | 02/24/2014 | $2,000 | $2,000 | $0 | A - Amendment | Citation has been deleted. | |
| 4. | 01004A | Serious | 19100333 A | 01/21/2014 | 02/24/2014 | $1,500 | $0 | $0 | Q - National Office Adjustment | ||
| 5. | 01004B | Serious | 19100335 A01I | 01/21/2014 | 02/24/2014 | $0 | $0 | $0 | Q - National Office Adjustment | ||
| 6. | 02001 | Other | 30039 | 01/21/2014 | 01/27/2014 | $0 | $750 | $0 | I - Informal Settlement |
Investigation Summary
On August 12, 2013, Employee #1 was troubleshooting a 480-volts HVAC unit, which was located on a concrete pad on the side of a two-story brick residence building. The unit was a Heil, Model Number PHB 324000K000 C1 and Serial Number C100342805. It weighed 3.5 ton and was 41 in. long by 31.5 in. wide by 47 in. tall. The unit had a 3-blade fan and the opening where the capacitor was located was 18.5 in. by 31.5 in. Employee #1 was not using a rubber or insulating kneeling pad nor wearing any personal protection equipment (i.e., gloves or safety glasses). He was on his knees with his left hand on the left side of the metal unit near the capacitor and his right hand was on the right side of the unit. The capacitor was a mini generator that provided power for the HVAC unit. When he contacted the capacitor and the unit, Employee #1 received an electric shock that electrocuted him. There was a fluke voltage meter and a set of wire cutters lying beside the three-terminal capacitor. Employee #1 had an electrical burn on his left hand to indicate the point entry of the electrical current and a burn on his right hand to indicate the exit point. The energy to the unit was also not isolated.
Keywords: MAINTENANCE, ELECTROCUTED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 317008480 | Fatality | Electric Shock | Heating, air conditioning, and refrig. mechanics |