Inspection: 315315416 - Alameda County General Services Agency

Inspection Information - Office: Oakland District Office

 

Inspection Nr: 315315416
Report ID: 0950614
Date Opened: 09/07/2011

Site Address:
Alameda County General Services Agency
5325 Broder Blvd
Dublin, CA 94568

Mailing Address:
125 12th St, Ste 300, Oakland, CA 94607

Union Status: Union

SIC:9223

NAICS: 922140/Correctional Institutions


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 12/02/2011

Emphasis:

Case Closed: 11/21/2012


Related Activity
Type Activity Nr Safety Health
Accident 361579691
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 4 1 5
Initial Penalty $31,500 $0 $0 $0 $0 $31,500
Current Penalty $19,005 $0 $0 $450 $0 $19,455
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2940 C 12/06/2011 12/30/2011 $335 $3,375 $0 12/16/2011 F - Formal Settlement  
2. 02001 Serious 2944 C01 12/06/2011 12/30/2011 $335 $3,375 $0 12/16/2011 F - Formal Settlement  
3. 03001 Serious 2944 E02 12/06/2011 12/30/2011 $18,000 $18,000 $0 12/16/2011 F - Formal Settlement  
4. 04001 Other 3210 D 12/06/2011 12/30/2011 $450 $3,375 $0 12/16/2011 F - Formal Settlement  
5. 05001 Serious 2944 H01 12/06/2011 12/30/2011 $335 $3,375 $0 12/16/2011 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202587028
Event: 09/06/2011
Employee Is Burned in Electrical Arc Flash

On September 6, 2011, an electrician with the Alameda County General Services Agency, was part of a four-person crew trouble-shooting displaced insulators in 12KV "B" bus bar switchgear. After reviewing the panel circuit diagram, the crew shut off bus bar "B" and the team tested for power. Employee #1 checked the phases with a tick tester to ensure that the circuits were not energized. He then used an Ideal multi-meter (rated for 600 volts maximum) and found phase "A" to ground indicated 84 volts, Phase "B" to ground indicated 83.5 volts, and Phase "C" indicated 84.5 volts. To locate the source of the residual power, Employee #1 went to the back of the panel, retested the wires with the tick tester in the same sequence, and no power registered. As he placed the meter's positive prong on the phase "C" conductor and the negative prong on the ground conductor, an arc flash occurred. Employee #1 and two other employees were transported to Eden Medical Center. Employee #1 was transferred to St. Francis Hospital's burn unit, where he was admitted for treatment of second-degree burns. The other two employees were released after evaluation.

Keywords: BURN, ELECTRIC ARC, INSULATOR, ELECTRICIAN, ELECTRIC METER, TEST EQUIPMENT, ELECTRIC CONDUCTOR, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 315315416 Hospitalized injury Other Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.