Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 315298091 - Nardone Electrical Corporation

Inspection Information - Office: North Boston

Nr: 315298091Report ID: 0134000Open Date: 03/01/2011

Nardone Electrical Corporation
Hanscom Airforce Base, Building 1435
Bedford, MA 01730
Union Status: NonUnion
SIC: 1731/Electrical Work
NAICS: 238210/Electrical Contractors
Mailing: 100 Winchester Street, Medford, MA 02155

Inspection Type:Complaint
Scope:Complete Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:03/01/2011
Emphasis: S:Commercial Constr, S:ElectricalClose Case:08/23/2011

Related Activity:TypeIDSafetyHealth
 Complaint207859307 Yes  

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 1 3
Initial Penalty $16,170 $0 $0 $0 $0 $16,170
Current Penalty $7,000 $0 $0 $2,600 $0 $9,600
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 19260095 A 07/27/2011 08/02/2011 $2,600 $5,390 $0 I - Informal Settlement
  2. 01002 Serious 19260416 A01 07/27/2011 08/01/2011 $3,500 $5,390 $0 I - Informal Settlement
  3. 01003 Serious 19260416 A03 07/27/2011 08/01/2011 $3,500 $5,390 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 200776458Event: 02/05/2011Employees Are Injured By Electrical Burn
On February 5, 2011, Employee # 1 and Employee # 2 were employed by Nardone Electrics. Employee # 1 and Employee # 2 were installing a replacement of an Automatic Transfer Switch (ATS) and related components for a building Uninterrupted Power Supply (UPS). The generator system failed which led to a transfer of building power to the UPS. Employee # 1 and Employee # 2 installed temporary wiring (welding leads) to bypass the ATS to provide continued power to the computer systems. After the workers completed the ATS replacement they turned the main switch on the Main Service Switch (MSS) panel to OFF and begin pulling the three phase permanent wiring into this cabinet. The grounding wire came in contact with energized 480 volt bus bars behind and above the main switch causing an arc flash. Employee # 1 and Employee # 2 sustained electrical burns.
Keywords: electric arc, electrician
Inspection Degree Nature Occupation
1 315298091 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 315298091 Hospitalized injury Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.