Inspection Detail
Inspection: 314860651 - Hawkins Electric Inc Dba Hawkins Electric
Inspection Information - Office: Los Angeles District Office
Site Address:
Hawkins Electric Inc Dba Hawkins Electric
6000 Sepulveda Blvd.
Culver City, CA 90230
Mailing Address:
1005 E. Las Tunas Dr. #124, San Gabriel, CA 91776
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/17/2012
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/15/2012
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 102758562 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 1 | 2 | |||
Current Violations | 2 | 2 | ||||
Initial Penalty | $1,575 | $0 | $0 | $85 | $0 | $1,660 |
Current Penalty | $0 | $0 | $0 | $950 | $0 | $950 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 1512 B | 01/17/2012 | 02/19/2012 | $50 | $85 | $0 | 01/23/2012 | F - Formal Settlement | |
2. | 02001 | Other | 23200002 A | 01/17/2012 | 01/20/2012 | $900 | $1,575 | $0 | 01/23/2012 | F - Formal Settlement |
Investigation Summary
At approximately 12:15 p.m. on October 10, 2011 Employee #1, a journeyman electrician, was performing electric work in an excavation at a Westfield mall. He was in communication via cell phone with a Westfield employee, who was deenergizing an exposed conductor. The Westfield employee had switched off the associated circuit breaker and remained in control of the circuit breaker panel. Employee #1 tested the conductor with a volt meter and found it to be deenergized. While stripping a wire to place a wire nut he sustained an electric shock. Employee #1 was hospitalized at UCLA medical center for treatment. Evidence indicated that the Westfield employee inadvertently reenergized the exposed conductor.
Keywords: ELEC INSULATION, EXCAVATION, ELECTRICAL TESTING, ELECTRICIAN, CONSTRUCTION, LOCKOUT, CIRCUIT BREAKER, ELECTRIC CONDUCTOR, ELECTRIC SHOCK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 314860651 | Hospitalized injury | Electric Shock | Electricians |