Powered by GoogleTranslate

Inspection Detail

Inspection: 314858994 - La County Mta

Inspection Information - Office: Los Angeles District Office

 

Inspection Nr: 314858994
Report ID: 0950641
Date Opened: 04/13/2011

Site Address:
La County Mta
284 S. Santa Fe Ave.
Los Angeles, CA 90013

Mailing Address:
, , 00000

Union Status: Union

SIC:4111

NAICS: 485111/Mixed Mode Transit Systems


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 08/16/2011

Emphasis:

Case Closed: 10/06/2012


Related Activity
Type Activity Nr Safety Health
Accident 102757226
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $5,060 $0 $0 $0 $0 $5,060
Current Penalty $1,125 $0 $0 $0 $0 $1,125
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2944 H01 09/15/2011 09/20/2011 $1,125 $5,060 $0 10/14/2011 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202543062
Event: 04/11/2011
Electric Shock & Burn - Contact with Energized Parts

A rail inspector for a transit authority was working on a circuit-modification project. The project included dividing a 750-volt dc bus into two sections, north and south. The inspector opened the circuit in the rail-yard substation, but he did not lock it out or tag it. After testing the bus with a voltmeter, he used a scissor lift to reach a junction box. As he was removing the bolts for the junction box cover, he received an electric shock and sustained third-degree burns to his left hand. The employer's accident investigation team reported that there was a possibility that the bus was accidentally energized by a combination of a knife switch for the disconnect switch being in the closed position and a fault in the control wiring to activate the contactor in the disconnect switch.

Keywords: BURN, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314858994 Non Hospitalized injury Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close