Inspection: 314709346 - Pacific Gas & Electric

Inspection Information - Office: Southwest Area Office

 

Inspection Nr: 314709346
Report ID: 0936100
Date Opened: 08/24/2010

Site Address:
Pacific Gas & Electric
Black Oak Casino 19400 Tuolume Road
Tuolume, CA 95379

Mailing Address:
77 Beale Street Room 2850 Mail Code B23h, San Francisco, CA 94105

Union Status: Union

SIC:1623

NAICS: 237130/Power and Communication Line and Related Structures Construction


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/15/2011

Planning Guide: Safety-Construction

Emphasis: S:Commercial Constr, S:Electrical

Case Closed: 07/27/2012


Related Activity
Type Activity Nr Safety Health
Accident 101781474
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 2 2
Initial Penalty $21,000 $0 $0 $0 $0 $21,000
Current Penalty $14,000 $0 $0 $0 $0 $14,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260550 A15 I 02/15/2011 02/25/2011 $7,000 $7,000 $0 03/01/2011 F - Formal Settlement  
2. 01002 Serious 19260600 A03 II 02/15/2011 02/25/2011 $7,000 $7,000 $0 03/01/2011 F - Formal Settlement Citation has been deleted.
3. 01003 Serious 19260950 B01 02/15/2011 02/25/2011 $7,000 $7,000 $0 03/01/2011 F - Formal Settlement  

Investigation Summary

Investigation Nr: 314709346
Event: 08/20/2010
Electric Shock - Contact with Overhead Line thru Boom

An equipment operator for an electric utility was working alone, operating a highway hydraulic-pressure digger. He was digging four holes for new utility poles for a new overhead power line. He used the digger to dig three of the holes and went to the location for the final hole. This location was directly under a 17.6-kilovolt overhead power line. The worker sat in the operator's station at the back of the truck bed operating the controls and raising the boom. The lowest overall working height of the digger was 6.6 meters, and the maximum sheave height was 9.1 meters, based on a 1-meter chassis-frame height. The overhead line was 8.2 meters above the ground. The digger was facing down an incline, and the worker's upward line of sight was obstructed by a factory-installed umbrella. As the worker raised the boom, it contacted the power line, energizing the truck. The worker got off the truck without incident, but was electrocuted when he contacted the digger's auger and fell onto an outrigger. A grass fire started near the truck after it became energized.

Keywords: DIGGER-DERRICK, OVERHEAD POWER LINE, ELECTRICAL, BOOM, ELECTROCUTED, E GI IA, ELEC UTILITY WORK, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314709346 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.