Inspection Detail
Inspection: 314301029 - Mp Technologies, Llc
Inspection Information - Office: Austin Area Office
Site Address:
Mp Technologies, Llc
6071 Hwy 331
Bellville, TX 77418
Mailing Address:
14140 N. Cypress Houston, Cypress, TX 77429
Union Status: Union
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/15/2010
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 01/11/2011
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 100605708 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 6 | 8 | |||
Current Violations | 1 | 6 | 7 | |||
Initial Penalty | $10,600 | $0 | $0 | $0 | $0 | $10,600 |
Current Penalty | $5,600 | $0 | $0 | $0 | $0 | $5,600 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260950 C01 II | 12/10/2010 | 12/16/2010 | $5,600 | $5,600 | $0 | I - Informal Settlement | ||
2. | 01002 | Serious | 19260955 C04 II | 12/10/2010 | 12/16/2010 | $5,000 | $5,000 | $0 | I - Informal Settlement | Citation has been deleted. | |
3. | 02001 | Other | 19040029 B01 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | I - Informal Settlement | ||
4. | 02002 | Other | 19040029 B01 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | I - Informal Settlement | ||
5. | 02003 | Other | 19040029 B01 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | I - Informal Settlement | ||
6. | 02004 | Other | 19040029 B02 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | I - Informal Settlement | ||
7. | 02005 | Other | 19040029 B02 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | I - Informal Settlement | ||
8. | 02006 | Other | 19040029 B02 | 12/10/2010 | 12/16/2010 | $0 | $0 | $0 | - |
Investigation Summary
A power line worker was in an aerial lift, installing new overhead power line conductors as part of a project to upgrade an existing 12.47-kilovolt overhead power line (7.2 kilovolts to ground) to a 34.5-kilovolt line (19.9 kilovolts to ground). The employee was lifting a new conductor onto a dolly when his spotter saw an electric arc. The power line worker fell to the bottom of the aerial lift bucket, and the spotter lowered the injured employee to the ground. The employee received cardiopulmonary resuscitation on site and was airlifted to a hospital, where he died. He had been electrocuted.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CPR, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 314301029 | Fatality | Electric Shock | Electrical power installers and repairers |