Powered by GoogleTranslate

Inspection Detail

Inspection: 313388506 - Dignity Health Dba Mercy Hospitals Of Bakersfield

Inspection Information - Office: Bakersfield District Office

 

Inspection Nr: 313388506
Report ID: 0950647
Date Opened: 03/15/2013

Site Address:
Dignity Health Dba Mercy Hospitals Of Bakersfield
2215 Truxtun Ave
Bakersfield, CA 93301

Mailing Address:
, , 00000

Union Status: Union

SIC:8062

NAICS: 622110/General Medical and Surgical Hospitals


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/06/2013

Emphasis:

Case Closed: 08/27/2013


Related Activity
Type Activity Nr Safety Health
Accident 102627890
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $51,750 $0 $0 $0 $0 $51,750
Current Penalty $36,000 $0 $0 $0 $0 $36,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2944 C 05/08/2013 05/18/2013 $6,750 $6,750 $0 06/05/2013 J - ALJ Decision  
2. 02001 Serious 29400002 A 05/08/2013 05/18/2013 $6,750 $22,500 $0 06/05/2013 J - ALJ Decision  
3. 03001 Serious 29400006 A 05/08/2013 05/18/2013 $22,500 $22,500 $0 06/05/2013 J - ALJ Decision  

Investigation Summary

Investigation Nr: 202458097
Event: 03/06/2013
Burn - Electrical Fault in Transformer Control Panel

At approximately 7:30 a.m. on March 6, 2013, an employee was working for Dignity Health, dba Mercy Hospitals of Bakersfield, CA. The employer was a hospital serving the Bakersfield and Kern county markets for in-house and outpatient treatment. The hospital also had an emergency treatment area that was always open. Employee #1 was a fulltime permanent employee of the hospital. His occupation was not provided. Employee #1 was using test equipment intended for use at voltages of no higher than 750 volts to test the fuses in a 12 kV electrical panel. The panel was a Square D panel, with Serial Number 49H-50427. It controlled a General Electric 12 kV transformer. When Employee #1 touched a fuse with the tester's electrodes, an arc flash occurred. Employee #1 was knocked back approximately 6 feet (1.8 meters), and he sustained burns. Among the causal factors was that Employee #1 was not a qualified employee, certified to work on such a high voltage. Further, he was using equipment rated at 750 volts to check a fuse on a 12 kV line. The employer notified the Division at 10:00 a.m. that same day.

Keywords: BURN, E GI II, FUSE, ELECTRIC ARC, ELECTRICAL, PPE, ELECTRICAL WORK, ELECTRICAL CABINET, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 313388506 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.