Powered by GoogleTranslate

Inspection Detail

Inspection: 313385551 - Southern California Edison

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 313385551
Report ID: 0950642
Date Opened: 11/04/2011

Site Address:
Southern California Edison
Pole Pd 01780 S Randolf W/O Woodward
Bell, CA 90201

Mailing Address:
2244 Walnut Grove Ave, Rosemead, CA 91770

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 03/29/2012

Emphasis:

Case Closed: 11/17/2013


Related Activity
Type Activity Nr Safety Health
Accident 102625571
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1
Initial Penalty $18,000 $0 $0 $560 $0 $18,560
Current Penalty $0 $0 $0 $560 $0 $560
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A04 03/30/2012 04/04/2012 $560 $560 $0 04/18/2012 F - Formal Settlement  
2. 02001 Serious 2941 I 03/30/2012 04/04/2012 $0 $18,000 $0 04/18/2012 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 202457586
Event: 11/03/2011
Burn - Electrical Fault in Conductor

At around 7:22 a.m. on November 3, 2011, Employee #1 was working as a line worker, and Employee #2 was working as an apparatus technician. Both were employed by the electric utility Southern California Edison. The firm generated and distributed electric power. It had over 10,000 employees. Employee #1 had been working there for 8 years, 8 months in his current job title. Employee #2 had been working there for 3 years in his current job title. At the time of the accident, they were performing a regularly assigned task of removing a line conductor to isolate a circuit at an unmanned substation. The conductor was one of a set of line conductors energized at 16,000 volts. The conductors were ultimately connected to a potential transformer as three-phase conductors running in an underground conduit. Employees #1 and #2 were to perform two tasks. First, they were to ensure that there was no load on the transformer conductors. Then, they were to remove the connecting conductors from the line conductors. Employees #1 and #2 were working from the bucket of an elevated aerial lift. Employee #1 checked the connecting conductors with an inductive ammeter. It indicated that there was no load on the conductors. Employee #2 removed one of the two clamps from the line conductor. Then, while Employee #2 held the conductor steady, Employee #1 began to remove the second clamp. The injured employees were working within proximity of a witness who was observing their activities. During this procedure, an electrical fault occurred in the area of the second clamp and the transformer conductor. The ensuing electric arc caused second- and third-degree burns to the face, neck, and arms of both employees. The injured employees were transported to the Saint Francis Medical Center and then to the Grossman Burn Center. Employee #1 was hospitalized at the burn center for 8 days, and Employee #2 was hospitalized at the burn center for 5 days. The Division conducted interviews of the injured employees, their supervisor foreman, and all members of the crew on site at the time of the injury. The investigation concluded that there was a possibility of a hazardous induced voltage buildup and that provisions to isolate or insulate the employees had not been made.

Keywords: BURN, ELECTRIC ARC, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, LOCKOUT, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 313385551 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 313385551 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close