Inspection Detail
Inspection: 313122319 - City Of Concord (Coddle Creek Water Plant)
Inspection Information - Office: Nc Department Of Labor - Charlotte
Site Address:
City Of Concord (Coddle Creek Water Plant)
693 South Davidson Highway
Concord, NC 28026
Mailing Address:
P.O. Box 0308, Concord, NC 28026
Union Status: NonUnion
SIC:9511
NAICS: 924110/Administration of Air and Water Resource and Solid Waste Management Programs
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: LocalGovt
Safety/Health: Safety
Close Conference: 05/28/2009
Planning Guide: Safety-Manufacturing
Emphasis: S:Program Improvements
Case Closed: 01/08/2010
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102098688 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $11,375 | $0 | $0 | $0 | $0 | $11,375 |
| Current Penalty | $7,950 | $0 | $0 | $0 | $0 | $7,950 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citation Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100335 A01 I | 07/28/2009 | 08/05/2009 | $2,200 | $3,150 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19100132 D01 | 07/28/2009 | 08/05/2009 | $0 | $0 | $0 | - | ||
| 3. | 01002 | Serious | 19100333 A | 07/28/2009 | 08/05/2009 | $2,200 | $3,150 | $0 | I - Informal Settlement | ||
| 4. | 01003A | Serious | 19100333 B02 | 07/28/2009 | 08/05/2009 | $1,350 | $1,925 | $0 | I - Informal Settlement | ||
| 5. | 01003B | Serious | 19100147 C04 I | 07/28/2009 | 07/31/2009 | $0 | $0 | $0 | - | ||
| 6. | 01004 | Serious | 19100332 B01 | 07/28/2009 | 08/05/2009 | $2,200 | $3,150 | $0 | I - Informal Settlement |
Investigation Summary
On March 9, 2009, Employee #1 was servicing a water pump. After servicing the pump, he was unable to restart the pump and contacted his supervisor. The supervisor caught up with the employee at the pump's electrical control panel. Employee #1 had thrown the electrical disconnect and opened the panel cover. He checked inside the panel and saw no obvious faults such as blown fuses and decided to check the voltage with a voltmeter. With the panel cover still open, Employee #1 reenergized the circuitry. With the supervisor holding the voltmeter, Employee #1 took the leads and attempted to check the voltage when an arc flash occurred. Employee #1 sustained second and third degree burns on hands and was hospitalized. The employee was not wearing gloves.
Keywords: BURN, ELECTRIC ARC, REPAIR, PPE, GLOVE, HAND
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 313122319 | Hospitalized injury | Burn/Scald(Heat) | Machinery maintenance occupations |