Powered by GoogleTranslate

Inspection Detail

Inspection: 313024770 - Cleco Power, Llc

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 313024770
Report ID: 0625700
Date Opened: 07/29/2009

Site Address:
Cleco Power, Llc
Tangle Wood Loop Near Hwy.171
De Ridder, LA 70634

Mailing Address:
P.O. Box 5000, Pineville, LA 71361

Union Status: NonUnion

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 10/19/2009

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 03/30/2010


Related Activity
Type Activity Nr Safety Health
Accident 100559004
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 A 11/09/2009 11/16/2009 $0 $4,500 $0 12/02/2009 J - ALJ Decision  

Investigation Summary

Investigation Nr: 200555738
Event: 07/28/2009
Employee Is Electrocuted

This accident is the same as accident 200555753. Employees of different employers were killed. The Reports have been combined under this number. On July 28, 2009, Employee#2 and two coworkers were engaged in right-of-way land clearing operations. One coworker was operating the track Jarraff (boom saw) mechanical equipment to trim the trees along the electrical overhead lines. Another coworker was operating the chain saw to help to clear the pathway around the poles of the overhead lines. Employee #2 was engaged in the operation of mowing by the use of the John Deer 542 Loader (bush-hog) tractor. The three employees began the land clearing operation at approximately 9:00 a.m. During this operation, the top of the tree fell on the power line after being cut by the mechanical boom saw. As a result, the power line was brought down on top of the John Deere tractor operated by Employee #2. At approximately 11:00 a.m. the operator of the boom saw told Employee #2 not to dismount from the tractor or touch any part of the tractor. Within minutes, the boom saw operator removed the downed power line from the tractor with the mechanical boom saw and continued the land clearing operation. Meanwhile, part of the downed line was positioned in the trees. The chain saw operator asked to borrow the tractor to get gas for the chain saw. So, the chain saw operator left the worksite to get gas approximately which was 150 yards away. Approximately 15 minutes later, Employee #1, the power utility employee, entered the worksite to investigate the power outage reported. Employee #1 was dispatched to repair the downed power line. The boom saw asked Employee #1 where is his glove? Employee #1 replied, "It only kills once." Employee #1 told two employees of the subcontractor that the down power line was not energized. Employee #1 picked up the power line with his bare hands in attempt to free part of the line stuck in the tree top. Employee #2 also grabbed the line without gloves and began to tug on it in the attempt to free it from the tree. The line remained stuck in the top of the tree. While Employee #1 and Employee #2 continued to tug the line, the boom saw operator was told by Employee #1 to use the mechanical boom saw to free the line from the tree top. They agreed to pull the downed line towards the pole. The distance between the electrical pole and the top of the tree where the line was positioned was approximately 30 ft. Employee #1 and Employee #2 were approximately 10 ft apart. The distance between the deenergized section of the downed power line and live components were approximately 36-in. As Employee #1 and Employee #2 continued to tug the line from the tree, the boom mechanical saw engaged in tugging the line causing the deenergized line to make contact with live components on the pole. Employee #1 and Employee #2 suffered an electrical shock of 19,960 volts. When the boom saw operator observed Employee #1 and Employee #2 were being shocked, he used the boom saw to cut the line. Emergency services were summoned. Employee #1 did not have a pulse and was pronounced dead at the scene. Employee #2 still had a faint pulse and was airlifted to the hospital and eventually died.

Keywords: ELECTRIC ARC, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 313024770 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.