Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 311729537 - Lehigh Southwest Cement Company

Inspection Information - Office: Ca Sacramento M&T District Office

Nr: 311729537Report ID: 0950651Open Date: 03/22/2010

Lehigh Southwest Cement Company
15390 Wonderland Boulevard
Redding, CA 96003
Union Status: Union
SIC: 1422/Crushed and Broken Limestone
NAICS: 212312/Crushed and Broken Limestone Mining and Quarrying

Inspection Type:Accident
Scope:Complete Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:04/26/2010
Emphasis: L:TunnelClose Case:06/14/2012

Related Activity:TypeIDSafetyHealth
 Accident101510493    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 1 6 7
Current Violations 1 4 5
Initial Penalty $0 $0 $10,000 $2,885 $0 $12,885
Current Penalty $0 $0 $9,000 $1,985 $0 $10,985
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Repeat 342 A 04/29/2010 05/04/2010 $9,000 $10,000 $0 05/12/2010 J - ALJ Decision
  2. 02001 Other 23400017 A02 04/29/2010 03/14/2012 $1,200 $1,200 $0 05/12/2010 W - Empr Withdrew
Deleted 3. 02002 Other 3382 A 04/29/2010 05/04/2010 $0 $450 $0 05/12/2010 J - ALJ Decision
  4. 02003 Other 3277 J04 04/29/2010 05/16/2010 $225 $225 $0 -
  5. 02004 Other 3277 K 04/29/2010 05/16/2010 $335 $335 $0 -
Deleted 6. 02005 Other 3212 A2A 04/29/2010 05/30/2010 $0 $450 $0 05/12/2010 J - ALJ Decision
  7. 02006 Other 3212 AB1 04/29/2010 05/16/2010 $225 $225 $0 -

Accident Investigation Summary
Summary Nr: 201510690Event: 02/01/2010Employee Is Burned By Arc Flash
Employee #1, an electrician working for Lehigh Southwest Cement Company, was working on a MCC panel. It had 480 volts and three phase energized buss bars behind a steel back plate. Employee #1 had two screwdrivers and a pair of wire cutters sitting on the tray at the bottom of the panel. One of the screwdrivers began to roll, and he went to secure it. However, the end of the screwdriver went under a narrow slot at the bottom of the back plate. It contacted the 480 volts buss bar, resulting in an arc flash. The arc flash contacted his right hand between his thumb and index finger. He was transported to the local hospital for burn treatment and then flown to the UC Davis Burn Center, where he was hospitalized for two nights.
Keywords: burn, electrical, finger
Inspection Degree Nature Occupation
1 311729537 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.