Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 3 1 4
Initial Penalty $4,875 $0 $0 $750 $0 $5,625
Current Penalty $4,875 $0 $0 $750 $0 $5,625
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Serious 618037501 05/19/2008 05/27/2008 $1,125 $1,125 $0 I - Informal Settlement
  2. 01002A Serious 19100146 C01 05/19/2008 06/01/2008 $1,875 $1,875 $0 I - Informal Settlement
  3. 01002B Serious 19100146 C02 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  4. 01002C Serious 19100146 C04 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  5. 01003A Serious 19100147 C04 I 05/19/2008 06/01/2008 $1,875 $1,875 $0 I - Informal Settlement
  6. 01003B Serious 19100147 C04 IIA 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  7. 01003C Serious 19100147 C04 IIB 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  8. 01003D Serious 19100147 C04 IIC 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  9. 01003E Serious 19100147 C04 IID 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  10. 01003F Serious 19100147 C06 I 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  11. 01003G Serious 19100147 C07 I 05/19/2008 06/01/2008 $0 $0 $0 I - Informal Settlement
  12. 02001 Other 618038301 05/19/2008 06/01/2008 $750 $750 $0 I - Informal Settlement

Accident Investigation Summary
Summary Nr: 201043684 Event: 02/07/2008Employee Is Struck And Killed By Fan Blades
On February 8, 2008, Employee #1 was working as an HVAC technician. He was working alone. The computer overseeing a cooling tower on the penthouse level roof of the city hall building had picked up a vibration alarm. It was displaying the alarm on a device being monitored by Employee #1. Employee #1 sent himself to determine the reason for the alarm. Employee #1 entered the cooling tower without shutting off or locking out power to the unit. The vibration switch consisted of a steel ball resting on a pedestal, just below which was a spring-loaded platform. If the ball landed on the platform due to excessive fan vibration, a circuit was opened. It is believed that Employee #1 stood on an A-frame ladder to reset the vibration switch. When he removed the steel ball from the platform, the circuit closed and the unit began running. Employee #1's jacket was caught up in the shaft of the unit's fan, located immediately above the vibration switch. As Employee #1 was suspended by one arm, his head was struck repeatedly by the blades of the rotating fan. Employee #1 subsequently died from his injuries. There were no witnesses to the incident.
Keywords: head, maintenance, fan, fan blade, cooling tower, alarm, ladder, lockout, vibrations, struck by
Inspection Degree Nature Occupation
1 311638324 Fatality Cut/Laceration Engineering technicians, n.e.c.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.