Powered by GoogleTranslate

Inspection Detail

Inspection: 311491617 - Mcm Commercial Concrete

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 311491617
Report ID: 0626600
Date Opened: 11/15/2007

Site Address:
Mcm Commercial Concrete
9518 Grant Road
Houston, TX 77070

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:1771

NAICS: 238110/Poured Concrete Foundation and Structure Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/21/2007

Emphasis:

Case Closed: 03/17/2008


Related Activity
Type Activity Nr Safety Health
Accident 101764157
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $10,000 $0 $0 $0 $0 $10,000
Current Penalty $8,000 $0 $0 $0 $0 $8,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100332 B01 12/17/2007 12/26/2007 $2,500 $2,500 $0 I - Informal Settlement  
2. 01002A Serious 19100333 B02 IIB 12/17/2007 12/20/2007 $2,500 $2,500 $0 I - Informal Settlement  
3. 01002B Serious 19100333 B02 IIIA 12/17/2007 12/20/2007 $0 $0 $0 I - Informal Settlement  
4. 01002C Serious 19100333 B02 IIIB 12/17/2007 12/21/2007 $0 $0 $0 I - Informal Settlement  
5. 01002D Serious 19100333 B02 IIID 12/17/2007 12/21/2007 $0 $0 $0 I - Informal Settlement  
6. 01003 Serious 19100333 C02 12/17/2007 12/20/2007 $3,000 $5,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201763034
Event: 11/14/2007
Employee electrocuted repairing portable light tower

On November 14, 2007, Employee #1 was repairing the inoperable lights on a Magnum Products light tower, model MLT4060, that was powered by a Marathon Electric 120/240-volt diesel generator, serial #630491. The unit consisted of the trailer-mounted generator, the diesel engine, and a telescoping mast supporting four metal-halide lamps in weatherproof enclosures. The light tower had come in from the field with the junction box, which contained the wiring connections, partially opened. Employee #1 removed the cover of the junction box and determined that one of the conductors had become loose. He was apparently attempting to reconnect the loose conductor when he contacted the uninsulated end and was electrocuted. Employee #1 had worked on the light towers many times before. It was not clear why he had the generator running and the main circuit breaker closed, thus energizing the conductors, while he was reconnecting the loose conductor.

Keywords: REPAIR, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, LOCKOUT, ELEC CIRC PART--MISC, ELECTRIC LIGHT--PORT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 311491617 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close