Powered by GoogleTranslate

Inspection Detail

Inspection: 310824891 - P G & E

Inspection Information - Office: Fresno District Office

 

Inspection Nr: 310824891
Report ID: 0950625
Date Opened: 03/10/2008

Site Address:
P G & E
4319 W Princeton Ave
Fresno, CA 93722

Mailing Address:
7205 National Drive, Livermore, CA 94550

Union Status: Union

SIC:4939

NAICS: 221121/Electric Bulk Power Transmission and Control


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/19/2008

Emphasis:

Case Closed: 10/06/2022


Related Activity
Type Activity Nr Safety Health
Accident 362054579
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 4 9
Current Violations 1 1 2
Initial Penalty $37,120 $0 $0 $7,870 $0 $44,990
Current Penalty $6,750 $0 $0 $420 $0 $7,170
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 B 05/19/2008 06/24/2008 $420 $420 $0 06/06/2008 F - Formal Settlement  
2. 01002 Other 1510 C 05/19/2008 06/24/2008 $0 $420 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
3. 01003 Other 1541 G01 C 05/19/2008 06/24/2008 $0 $280 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
4. 02001 Other 1510 B 05/19/2008 06/24/2008 $0 $6,750 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
5. 03001 Serious 1511 A 05/19/2008 06/24/2008 $0 $6,750 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
6. 04001 Serious 1514 A 05/19/2008 06/24/2008 $0 $6,750 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
7. 05001 Serious 3203 A07 D 05/19/2008 06/24/2008 $6,750 $6,750 $0 06/06/2008 F - Formal Settlement  
8. 06001 Serious 3328 A 05/19/2008 06/24/2008 $0 $8,435 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.
9. 07001 Serious 5416 C 05/19/2008 06/24/2008 $0 $8,435 $0 06/06/2008 D - Govt Dismissed Citation has been deleted.

Investigation Summary

Investigation Nr: 201490695
Event: 11/20/2007
Employee Sustains Burns to Face When Flammable Gas Ignites

On November 20, 2007, Employee #1, an equipment operator, was repairing a natural gas line leak in Fresno, California. Employee #1 was replacing a section of class Number 3 residential polypropylene plastic service line, which had 1 in. in diameter and 0.090-in. wall thickness. The gas line was damaged by an electrical crew, while removing tree roots to access the electrical conductors in a joint service trench. The gas line was damaged with a shovel causing a blowing gas leak. The gas line had pressure of 50 PSI and was covered with dirt to muffle the noise. A gas crew, together with Employee #1 and a gas construction foreman, were dispatched to repair the leak. An attempt was made to enlarge the excavation with a backhoe, but the roots caused the ground to rise as a unit. To mitigate further property damage the crew decided to cut away the roots using a saw. An attempt was made with a hand saw, but progress was slow, thus the crew decided to use a Bosch 18 volt cordless reciprocation saw. Employee #1 got into the excavation for positioning and energizing the saw, which ignited the flammable gas. Employee #1 got out from the excavation with only a flash burn to his face and irregular heart beat. He was hospitalized with nonserious injuries to his face and heart condition, which was determined as nonoccupational. Both, Employee #1 and the gas construction foreman were not aware that a cordless power tool would be an ignition source. Root cause for this event was the use of a spark producing power tool, which was an ignition source, in a flammable atmosphere.

Keywords: BURN, EXCAVATION, REPAIR, FIRE, IGNITION SYSTEM, GAS, SAW, GAS LEAK, FACE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310824891 Hospitalized injury Burn/Scald(Heat) Specified mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.