Powered by GoogleTranslate

Inspection Detail

Inspection: 310494463 - Access Air Conditioning

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 310494463
Report ID: 0950642
Date Opened: 02/26/2009

Site Address:
Access Air Conditioning
2585 E Washington Bl
Pasadena, CA 91107

Mailing Address:
Po Box 411145, Los Angeles, CA 90041

Union Status: NonUnion

SIC:7623

NAICS: 811412/Appliance Repair and Maintenance


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/09/2009

Emphasis:

Case Closed: 01/05/2010


Related Activity
Type Activity Nr Safety Health
Accident 102475084
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $0 $0 $0 $5,350 $0 $5,350
Current Penalty $0 $0 $0 $1,200 $0 $1,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 03/13/2009 03/18/2009 $850 $5,000 $0 03/30/2009 F - Formal Settlement  
2. 01002 Other 3203 A 03/13/2009 04/15/2009 $175 $175 $0 -  
3. 01003 Other 3395 E03 03/13/2009 04/15/2009 $175 $175 $0 -  

Investigation Summary

Investigation Nr: 202455101
Event: 02/16/2009
Employee Sustains Burns from Electric Arc Flash

At approximately 1:30 p.m. on February 16, 2009, Employee #1, an air conditioning technician, and a coworker, his supervisor, were repairing an air conditioning unit. The air conditioning unit was repeatedly tripping the circuit breaker. The coworker removed the metal face plate from the main electrical panel to determine the voltage. The coworker reset the circuit breaker and confirmed the voltage output of 240 volts and an amperage draw of 13 to 15 amps per phase. The coworker instructed the employee to replace the metal face cover, while the coworker tended to the thermostats. The employee put on his protective face shield, picked up the metal face panel cover and squatted in front of the electrical panel. Before he could replace the cover, an electrical flash occurred from within the main electrical panel pushing him backwards, burning his face, hands, arms and legs, and activating the automatic fire suppression sprinklers. Employee #1 sustained second and third degree burns to his face, hands, arms and legs, and was hospitalized. The employee was wearing a long sleeve cotton work shirt and cotton work pants. An electrician hired to repair the damage caused by the accident determined that an electrical short circuit had occurred in the electrical conduit on the roof supplying the air conditioning unit. Leaves were found in the conduit and the fault was repaired.

Keywords: BURN, ELECTRIC ARC, REPAIR, PPE, FIRE, ARM, FACE, HAND, LEG

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310494463 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close