Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/20/2006

Planning Guide: Safety-Construction

Emphasis: S:Construction (Cship)

Case Closed: 01/29/2007


Related Activity
Type Activity Nr Safety Health
Accident 101115608
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 3 3
Initial Penalty $22,500 $0 $0 $5,750 $0 $28,250
Current Penalty $0 $0 $0 $6,875 $0 $6,875
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 11/20/2006 11/30/2006 $5,000 $5,000 $0 -  
2. 01002 Other 23200003 11/20/2006 11/30/2006 $750 $750 $0 -  
3. 02001 Other 23200004 A02 11/20/2006 11/30/2006 $1,125 $22,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 202463758
Event: 08/23/2006
Employee burned in electrical flash fire

At approximately 7:00 a.m. on August 23, 2006, Employee #1, an electrician/service technician, was working alone while servicing a three-phase, 120-/208-volt electrical meter panel. He was disconnecting conductors from the generator and hooking them up to the main electric supply when his Allen wrench contacted a phase (bus bar) and meter base. This caused a short that resulted in a flash fire. Employee #1 sustained burns and was transported to Grossman Burn Center, where he remained hospitalized for about nine days. Subsequent investigation determined that the electrical panel was not effectively protected from unexpected or inadvertent energizing. The employer was cited for a violation of T8CCR 2320.4(a)(2).

Keywords: BURN, WORK RULES, ELECTRICIAN, FIRE, STRUCK AGAINST, CONSTRUCTION, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL BOX, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310193958 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.