Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 310097456 - Sunpower Electric

Inspection Information - Office: Ca Foster City District Office

Nr: 310097456Report ID: 0950613Open Date: 04/07/2010

Sunpower Electric
River Of Life Church. 1177 Laurelwood Rd.
Santa Clara, CA 95054
Union Status: NonUnion
SIC: 1731/Electrical Work
NAICS: 238210/Electrical Contractors
Mailing: 15641 Chemical Lane, Unit D, Huntington Beach, CA 92649

Inspection Type:Accident
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:05/04/2010
Close Case:07/09/2010

Related Activity:TypeIDSafetyHealth
 Accident101134625    

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $0 $0 $0 $5,125 $0 $5,125
Current Penalty $0 $0 $0 $5,125 $0 $5,125
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 342 A 05/04/2010 05/21/2010 $5,000 $5,000 $0 -
  2. 01002 Other 3203 A 05/04/2010 05/21/2010 $125 $125 $0 -

Accident Investigation Summary
Summary Nr: 201127545Event: 03/30/2010Burn - Electrical Fault In Electrical Cabinet
An engineering firm gave a punch list to an electrician. The list included checking for loose connections in a 480-volt, 150-ampere, three-phase circuit breaker cubicle. Because the electrician was only going to inspect the cabinet, and not perform any energized work, he left the cabinet energized. He intended to deenergize the cabinet if he found any loose objects or connections. However, the electrician, who was working alone at the time, began fastening a bracket for the circuit breaker. The bracket contacted the energized bus, creating an electrical fault and shocking the employee. The ensuing electric arc burned the employee's face. He was hospitalized for 2 days for second-degree burns to his cheeks and forehead. At the time of the accident, the employee was wearing gloves, work boots, and a hardhat. Safety glasses were on his forehead.
Keywords: burn, electric arc, e gi iv, electrical, electrician, electrical work, lockout, circuit breaker, electric shock, electrical fault
Inspection Degree Nature Occupation
1 310097456 Hospitalized injury Burn/Scald(Heat) Electricians

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close