Inspection Detail
Inspection Information - Office: Ca Foster City District Office | ||||
---|---|---|---|---|
Nr: 310097456 | Report ID: 0950613 | Open Date: 04/07/2010 | ||
Sunpower Electric | ||||
River Of Life Church. 1177 Laurelwood Rd. Santa Clara, CA 95054 | Union Status: NonUnion | |||
SIC: 1731/Electrical Work | ||||
NAICS: 238210/Electrical Contractors | ||||
Mailing: 15641 Chemical Lane, Unit D, Huntington Beach, CA 92649 | ||||
Inspection Type: | Accident | |||
Scope: | Partial | Advanced Notice: | N | |
Ownership: | Private | |||
Safety/Health: | Safety | Close Conference: | 05/04/2010 | |
Close Case: | 07/09/2010 | |||
Related Activity: | Type | ID | Safety | Health |
Accident | 101134625 |
Violation Summary | ||||||
---|---|---|---|---|---|---|
Serious | Willful | Repeat | Other | Unclass | Total | |
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $0 | $0 | $0 | $5,125 | $0 | $5,125 |
Current Penalty | $0 | $0 | $0 | $5,125 | $0 | $5,125 |
FTA Amount | $0 | $0 | $0 | $0 | $0 | $0 |
Violation Items | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | ID | Type | Standard | Issuance | Abate | Curr$ | Init$ | Fta$ | Contest | LastEvent | |
1. | 01001 | Other | 342 A | 05/04/2010 | 05/21/2010 | $5,000 | $5,000 | $0 | - | ||
2. | 01002 | Other | 3203 A | 05/04/2010 | 05/21/2010 | $125 | $125 | $0 | - |
Accident Investigation Summary | ||||||
Summary Nr: 201127545 | Event: 03/30/2010 | Burn - Electrical Fault In Electrical Cabinet | ||||
An engineering firm gave a punch list to an electrician. The list included checking for loose connections in a 480-volt, 150-ampere, three-phase circuit breaker cubicle. Because the electrician was only going to inspect the cabinet, and not perform any energized work, he left the cabinet energized. He intended to deenergize the cabinet if he found any loose objects or connections. However, the electrician, who was working alone at the time, began fastening a bracket for the circuit breaker. The bracket contacted the energized bus, creating an electrical fault and shocking the employee. The ensuing electric arc burned the employee's face. He was hospitalized for 2 days for second-degree burns to his cheeks and forehead. At the time of the accident, the employee was wearing gloves, work boots, and a hardhat. Safety glasses were on his forehead. | ||||||
Keywords: burn, electric arc, e gi iv, electrical, electrician, electrical work, lockout, circuit breaker, electric shock, electrical fault | ||||||
Inspection | Degree | Nature | Occupation | |||
---|---|---|---|---|---|---|
1 | 310097456 | Hospitalized injury | Burn/Scald(Heat) | Electricians |