Powered by GoogleTranslate

Inspection Detail

Inspection: 309469393 - Americo, Inc.

Inspection Information - Office: Charleston Area Office

 

Inspection Nr: 309469393
Report ID: 0316400
Date Opened: 10/04/2006

Site Address:
Americo, Inc.
58 19th St.
Wheeling, WV 26003

Mailing Address:
One River Park, Mcmechen, WV 26040

Union Status: NonUnion

SIC:6512

NAICS: 531120/Lessors of Nonresidential Buildings (except Miniwarehouses)


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 10/05/2006

Emphasis: S:Electrical

Case Closed: 12/07/2006


Related Activity
Type Activity Nr Safety Health
Accident 100631357
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $3,000 $0 $0 $0 $0 $3,000
Current Penalty $3,000 $0 $0 $0 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 H03 I 11/15/2006 11/20/2006 $750 $750 $0 -  
2. 01002A Serious 19100332 B01 11/15/2006 11/20/2006 $750 $750 $0 -  
3. 01002B Serious 19100333 C02 11/15/2006 11/20/2006 $0 $0 $0 -  
4. 01003A Serious 19100334 C03 11/15/2006 11/20/2006 $750 $750 $0 -  
5. 01003B Serious 19100334 C01 11/15/2006 11/20/2006 $0 $0 $0 -  
6. 01004 Serious 19100335 A01 V 11/15/2006 11/20/2006 $750 $750 $0 -  

Investigation Summary

Investigation Nr: 200631422
Event: 10/04/2006
Employee Is Electrocuted While Testing Voltage

On October 4, 2006, Employee #1, a 63-year-old male electrician who was purported to have many years of experience with heavy industry electrical systems, was trying to test the voltage of the three-phase electrical service of a commercial building. Employee #1 was testing by touching the test leads of a meter to the top or "hot" contact of a series of knife switches that disconnected power to the rest of the building. A helper with no electrical training or experience was standing in close proximity, holding a digital multi-meter so that the Employee #1 could see the display. The meter was rated by the manufacturer as Category III, 1,000 volts. According to the helper, Employee #1 had repeatedly tried to test from one leg of the three-phase service to the ground leg. Each time the meter displayed "OL" or overload, the electrician withdrew one or both of the test probes, punched the "range" button on the meter, and then retested. Ultimately, Employee #1 removed one of the electrical protective gloves he was wearing. He again punched the range button on the meter and recontacted the test leads. After an arc and loud pop, the meter was blown out of the helper's hand. Employee #1 began to "sling his forearm like it was asleep or like he hit his crazy bone." He staggered to a wall and slid down to the floor. The helper summoned local emergency services. Employee #1 was transported to a nearby hospital, where he was pronounced dead. According to the power company, American Electric Power Co., each phase of the service was 2,400 volts to ground.

Keywords: ELEC PROTECT EQUIP, ELECTRIC ARC, PPE, ELECTRICAL TESTING, ELECTRICIAN, ELECTROCUTED, ELECTRIC METER, ELECTRIC SHOCK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309469393 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close