Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 308276658 - Connecticut Light & Power Company

Inspection Information - Office: Hartford

Nr: 308276658Report ID: 0112000Open Date: 01/26/2006

Connecticut Light & Power Company
300 Wethersfield Avenue (Bulkeley High)
Hartford, CT 06114
Union Status: Union
SIC: 4911/Electric Services
NAICS: 221122/Electric Power Distribution
Mailing: P.O. Box 270, Hartford, CT 06141

Inspection Type:Planned
Scope:Partial Advanced Notice:N
Ownership:Private
Safety/Health:Safety Close Conference:04/19/2006
Planning Guide: Safety-Construction Close Case:09/21/2006

Violation Summary
Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1 2
Initial Penalty $14,000 $0 $0 $0 $0 $14,000
Current Penalty $5,600 $0 $0 $5,600 $0 $11,200
FTA Amount $0 $0 $0 $0 $0 $0

Violation Items
# ID Type Standard Issuance Abate Curr$ Init$ Fta$ Contest LastEvent
  1. 01001 Other 19100269 A02 I 04/24/2006 04/28/2006 $5,600 $7,000 $0 F - Formal Settlement
  2. 01002 Serious 19100269 G01 04/24/2006 04/28/2006 $5,600 $7,000 $0 F - Formal Settlement

Accident Investigation Summary
Summary Nr: 200082535Event: 01/26/2006Employee Is Burned By Arc Flash
Employee #1 was engaged in routine annual maintenance to a network protector. The network protector is attached to a 23-kv transformer. The transformer steps the voltage down to 277/480. Employee #1 was removing the fuses so that special test equipment could be attached so the network protectors could be calibrated. The network protector was never deenergized. As Employee #1 removed the fuses, it makes contact with the metal cabinet causing an instant arc flash and intense fire. Employee #1 was taken to an area hospital for severe burns to the forehead. Employee #1 was hospitalized.
Keywords: burn, fuse, electric arc, heat, fire, forehead
Inspection Degree Nature Occupation
1 308276658 Hospitalized injury Burn/Scald(Heat) Occupation not reported

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.