Inspection Detail
Inspection: 307462317 - Southern California Edison
Inspection Information - Office: San Bernardino District Office
Site Address:
Southern California Edison
37000 E.Santa Fe St
Daggett, CA 92327
Mailing Address:
14660 Chestnut Ave, Westminster, CA 92683
Union Status: Union
SIC:4911
NAICS: 221122/Electric Power Distribution
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/13/2007
Emphasis:
Case Closed: 10/01/2007
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102493368 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $21,375 | $0 | $0 | $0 | $0 | $21,375 |
| Current Penalty | $2,700 | $0 | $0 | $0 | $0 | $2,700 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3203 A02 | 06/13/2007 | 06/20/2007 | $0 | $3,375 | $0 | 07/02/2007 | F - Formal Settlement | |
| 2. | 02001 | Serious | 2941 H11 | 06/13/2007 | 06/20/2007 | $2,700 | $18,000 | $0 | 07/02/2007 | F - Formal Settlement |
Investigation Summary
At approximately 12:30 p.m. on January 3, 2007, Employee #1, a foreman, and a crew of nine were replacing a deteriorated wooden H-frame structure carrying 115 kV overhead power lines. There were three conductors with light weight tubular steel poles. There was an energized high voltage line 230 kV approximately 60 ft from the de energized conductors. All the conductors were deenergized and were resting on the ground. Employee #1 and a coworker, an apprentice, were trying to put the center phase conductor on the suspension shoe on the crossarm. Employee #1 was in the basket of a crane, Altec 92 foote crane, and the conductor was on the hook of the crane, a Y2K Electric line truck-crane. The boom of the electric truck was not long enough to reach the suspension shoe. Employee #1 was holding the hook of the lift in one hand and the conductor in the other hand. He placed himself between two different ground potentials due to induced voltage caused by the 230KV power lines. He received a severe shock which caused second and third degree burns on both hands, which required hospitalization.
Keywords: BURN, ELECTRIC SHOCK, HAND
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 307462317 | Hospitalized injury | Electric Shock | Supervisors; electricians & power transm. install. |
Translate