Inspection: 3052305 - Golden Anchor Restaurant

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 3052305
Report ID: 0453710
Date Opened: 08/13/1986

Site Address:
Golden Anchor Restaurant
Rt 4 Washburn Switch Rd
Shelby, NC 28150

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5812

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/13/1986

Emphasis:

Case Closed: 10/27/1986


Related Activity
Type Activity Nr Safety Health
Accident 360768444
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 8 8
Current Violations 8 8
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100303 B02 09/16/1986 09/19/1986 $0 $0 $0 -  
2. 01002 Other 19100303 C 09/16/1986 09/19/1986 $0 $0 $0 -  
3. 01003 Other 19100304 F04 09/16/1986 09/19/1986 $0 $0 $0 -  
4. 01004 Other 19100304 F05 V 09/16/1986 09/19/1986 $0 $0 $0 -  
5. 01005 Other 19100305 B01 09/16/1986 09/19/1986 $0 $0 $0 -  
6. 01006 Other 19100305 B02 09/16/1986 09/19/1986 $0 $0 $0 -  
7. 01007 Other 19100305 G01 IIIA 09/16/1986 09/19/1986 $0 $0 $0 -  
8. 01008 Other 19100305 G02 III 09/16/1986 09/19/1986 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 14250872
Event: 08/03/1986
ELECTRIC SHOCK - GROUND FAULT IN UTILIZATION EQUIPMENT

AN EMPLOYEE WHO WAS WET-MOPPING A CONCRETE FLOOR SLIPPED. AS HE WAS FALLING, HE GRABBED THE HANDLE OF A 120-VOLT METAL FOOD COOLER. THE JARRING OF THE COOLER CAUSED A BARE SPOT ON THE UNGROUNDED CIRCUIT CONDUCTOR IN THE COOLER'S ELECTRIC POWER SUPPLY CORD TO CONTACT THE METAL FRAME WHERE THE CORD ENTERED. THE ELECTRIC CORD WAS A TWO-CONDUCTOR UNGROUNDED TYPE AND WAS PLUGGED INTO A RECEPTACLE ON THE END OF AN EXTENSION CORD SET USED AS PERMANENT WIRING. THE EMPLOYEE WAS ELECTROCUTED.

Keywords: ELECTRICAL, E GI VII, ELECTROCUTED, GROUND FAULT, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 3052305 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.