Powered by GoogleTranslate

Inspection Detail

Inspection: 304568876 - Intercontinental Terminals Co

Inspection Information - Office: Houston South Area Office

 

Inspection Nr: 304568876
Report ID: 0626700
Date Opened: 10/25/2001

Site Address:
Intercontinental Terminals Co
1943 Battleground Rd
Deer Park, TX 77536

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:5171

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/13/2001

Emphasis:

Case Closed: 06/04/2002


Related Activity
Type Activity Nr Safety Health
Accident 101930279
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,900 $0 $0 $0 $0 $4,900
Current Penalty $2,940 $0 $0 $0 $0 $2,940
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 12/19/2001 01/21/2002 $2,940 $4,900 $0 01/15/2002 R - Review Commission  

Investigation Summary

Investigation Nr: 201922119
Event: 09/13/2001
Employee Burned By Steam

On September 13, 2001, Employee #1 was opening a 12-inch gate valve to put the Number 150 steam back in service. The 12-inch valve was bolted to a vertical 12-inch line. All of the nuts lacked two or three threads. Condensate had built up on the top side of the gate. Employee #1 opened the gate about 0.25 inch. Due to the condensate, Number 150 steam, and the nuts not completely threaded the pipe separated from the valve. The top pipe flange and gate valve flange separated when the bolt threads were stripped. The release of steam and condensate burned Employee #1 on 99 percent of his body with second- and third-degree burns, killing him.

Keywords: BURN, STEAM, HIGH PRESSURE, PIPE, PRESSURE RELEASE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304568876 Fatality Burn/Scald(Heat) Miscellaneous plant and system operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.