Inspection Detail
Inspection: 304472921 - Insulations, Inc. Dba Empire Scaffold
Inspection Information - Office: Baton Rouge Area Office
Site Address:
Insulations, Inc. Dba Empire Scaffold
102 Mill Street
Hodge, LA 71247
Mailing Address:
8500 Frontage Rd., Monroe, LA 71202
Union Status: NonUnion
SIC:1799
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 08/26/2001
Emphasis:
Case Closed: 01/28/2003
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100552637 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $17,100 | $0 | $0 | $0 | $0 | $17,100 |
| Current Penalty | $8,550 | $0 | $0 | $0 | $0 | $8,550 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260405 A02 IIE | 02/12/2002 | 02/15/2002 | $2,100 | $6,300 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19260405 A02 IIG | 02/12/2002 | 02/12/2002 | $2,100 | $2,250 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19260405 J01 I | 02/12/2002 | 02/15/2002 | $2,100 | $6,300 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19260416 E01 | 02/12/2002 | 02/15/2002 | $2,250 | $2,250 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 12:30 a.m. on August 25, 2001, Employee #1 was dismantling scaffolding inside a recovery boiler. A light stringer had been set up to illuminate the boiler. The light bulb receptacle located at the north end of the scaffold deck was missing a bulb and the plastic bulb guard was damaged. Employee #1 was walking by the bulb receptacle when his leg contacted the 124 volt socket. He received an electrical shock that resulted in his suffering cardiac arrest. The 124-volt light was not protected by a ground fault circuit interrupter and it was plugged into an electrical outlet equipped with a 20 ampere breaker. The metal boiler was grounded. It took approximately 45 minutes to remove Employee #1 from inside the boiler; he was pronounced dead at the scene.
Keywords: LIGHTING CIRCUIT, DISMANTLING, INADEQUATE MAINT, WORK RULES, ELECTROCUTED, LIGHTING FIXTURE, STRUCK AGAINST, CONSTRUCTION, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 304472921 | Fatality | Electric Shock | Occupation not reported |
Translate