Powered by GoogleTranslate

Inspection Detail

Inspection: 304408073 - O C Tanner Co

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 304408073
Report ID: 0854910
Date Opened: 04/18/2001

Site Address:
O C Tanner Co
1930 S State St
Salt Lake City, UT 84115

Mailing Address:
1930 S State Street, Salt Lake City, UT 84115

Union Status: NonUnion

SIC:3911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/10/2001

Planning Guide: Safety-Construction

Emphasis: S:Manufacturing

Case Closed: 08/10/2001


Related Activity
Type Activity Nr Safety Health
Accident 362653701

Investigation Summary

Investigation Nr: 304408073
Event: 04/17/2001
Six Employees Injured By Steam From Ruptured Tank

Six employees were injured when a drum became pressurized to the point it ruptured. The system is an open system and is designed to not ever become pressurized. The exact method that the drum became pressurized is unclear. The normal lid of the drum was replaced with a lid that has a blower attached that direct the steam through the condenser. Even with the blower lid on the drum there are still openings around the blower unit as is not sealed. In addition, there was a door on the lid that had an opening. The blower did not work when checked after the accident, but it is unknown when it failed. Even if the blower unit failed, the system would not be closed and should not have pressurized. The blower was maintained on a regular preventive maintenance schedule. The drum was new and appeared to be the correct type of drum for the process. There is a possibility that a steam pocket formed under the old sludge in the drum and built up sufficient pressure to rupture the drum. The drum goes through many heating and cooling cycles until the drum is full enough to be sent for disposal. The process is carried out once or twice a week depending on how much wastewater there is to dispose. All six employees were hospitalized for burns.

Keywords: BURN, RUPTURE, STEAM, TANK, PRESSURE RELEASE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
2 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
3 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
4 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
5 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
6 304408073 Hospitalized injury Burn/Scald(Heat) Hand painting, coating and decorating occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.