Powered by GoogleTranslate

Inspection Detail

Inspection: 304086788 - Bogot Services, Inc

Inspection Information - Office: Chicago South Area Office

 

Inspection Nr: 304086788
Report ID: 0521700
Date Opened: 09/01/2001

Site Address:
Bogot Services, Inc
900 N. Lake Shore Drive
Chicago, IL 60611

Mailing Address:
730 N. Busse Highway, Park Ridge, IL 60068

Union Status: Union

SIC:1711

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/07/2002

Emphasis:

Case Closed: 04/04/2002


Related Activity
Type Activity Nr Safety Health
Accident 100031236
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $5,000 $0 $0 $0 $0 $5,000
Current Penalty $4,000 $0 $0 $0 $0 $4,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 B02 I 02/21/2002 04/12/2002 $2,000 $2,500 $0 I - Informal Settlement  
2. 01002 Serious 19100335 A02 I 02/21/2002 03/26/2002 $2,000 $2,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200031441
Event: 08/31/2001
Employee electrocuted while servicing chiller unit

At 10:15 a.m. on August 31, 2001, Employee #1 arrived at a building in Chicago where he was to perform a regularly scheduled preventive maintenance check on the chiller units. Upon his arrival, the building engineer informed him that the #3 fan motor was not working and gave him access to the chiller fans. At approximately 4:00 p.m., a janitor found Employee #1, dead, lying between two fan motors. The disconnect for the #3 fan motor was open. The junction box below the #4 fan motor disconnect was also open and the wires coming from it had been cut. A pair of wire cutters with burn marks on the handle were found next to Employee #1, who also had burn marks on his right hand. The equipment being worked on had not been locked out.

Keywords: BURN, MAINTENANCE, REPAIR, ELECTRICAL, WORK RULES, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304086788 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.