Powered by GoogleTranslate

Inspection Detail

Inspection: 303982367 - C.W. Wright Construction Company, Incorporated

Inspection Information - Office: Department Of Labor, Licensing And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 303982367
Report ID: 0352460
Date Opened: 10/10/2000

Site Address:
C.W. Wright Construction Company, Incorporated
23404 Hurry Road
Clements, MD 20624

Mailing Address:
P.O. Box 1220, 11500 Ironbridge Road, Chester, VA 23831

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/11/2000

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 09/07/2001


Related Activity
Type Activity Nr Safety Health
Accident 100967397
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 1 1 2
Initial Penalty $14,350 $0 $0 $0 $0 $14,350
Current Penalty $5,150 $0 $0 $0 $0 $5,150
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 A02 IVA 02/20/2001 03/25/2001 $0 $3,600 $0 02/28/2001 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19100269 C01 02/20/2001 03/25/2001 $0 $5,600 $0 02/28/2001 F - Formal Settlement Citation has been deleted.
3. 01003 Serious 19100269 P04 IIIC 02/20/2001 02/23/2001 $5,150 $5,150 $0 02/28/2001 F - Formal Settlement  
4. 02001 Other 19100269 B01 I 02/20/2001 03/25/2001 $0 $0 $0 02/28/2001 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200966984
Event: 10/09/2000
Electric Shock - Contact with Overhead Line thru Boom

A second-class power line worker and a ground worker working for an electrical contractor were assigned by their general foreman and foreman to plumb a hot link holding a deenergized line and to spot paint the butt of a utility pole with epoxy paint. Earlier that day, the power line worker had been temporarily assigned to an aerial lift with a 27-meter-long boom. His regularly assigned aerial lift, which had a 14-meter-long boom, had been sent to the shop for maintenance. The power line worker parked the aerial lift directly under an energized 66-kilovolt overhead power line. (The reclosing devices for this power line had been disabled.) Instead of using their 7.3-meter-long fiberglass ladder to access the pole steps and climb the pole, he elevated himself in the aerial lift. He raised the metal portion of the boom into the energized power line and received an electric shock. The ground worker, who was mixing a small can of epoxy paint on the right side of the aerial lift truck with his arms leaning again the side of truck, was electrocuted. The power line worker was hospitalized for his injuries. Four days before the accident, a construction supervisor and a senior engineer for the electric utility owning the line had observed the power line worker performing the same task on a different pole. At that time, he had used a ladder to ascend the pole.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, BOOM, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303982367 Fatality Electric Shock Construction laborers
2 303982367 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close