Powered by GoogleTranslate

Inspection Detail

Inspection: 303608095 - Goodliffe Electric Inc.

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 303608095
Report ID: 0854910
Date Opened: 07/12/2000

Site Address:
Goodliffe Electric Inc.
2424 S 2050 W
Ogden, UT 84401

Mailing Address:
2424 South 2050 West, Ogden, UT 84401

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/01/2000

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Construction Fatalities

Case Closed: 12/31/2001


Related Activity
Type Activity Nr Safety Health
Accident 362652299
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $1,800 $0 $0 $0 $0 $1,800
Current Penalty $1,800 $0 $0 $0 $0 $1,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100147 D04 I 01/11/2001 01/31/2001 $450 $450 $0 -  
2. 01001B Serious 19100147 F02 I 01/11/2001 01/31/2001 $0 $0 $0 -  
3. 01002A Serious 19100333 A01 01/11/2001 01/31/2001 $450 $450 $0 -  
4. 01002B Serious 19100333 A02 01/11/2001 01/31/2001 $0 $0 $0 -  
5. 01002C Serious 19100333 B02 I 01/11/2001 01/31/2001 $0 $0 $0 -  
6. 01002D Serious 19100333 B02 IIB 01/11/2001 01/31/2001 $0 $0 $0 -  
7. 01002E Serious 19100333 C02 01/11/2001 01/31/2001 $0 $0 $0 -  
8. 01003A Serious 19100335 A01 01/11/2001 01/18/2001 $450 $450 $0 -  
9. 01003B Serious 19100335 A02 I 01/11/2001 01/31/2001 $0 $0 $0 -  
10. 01003C Serious 19100335 A02 II 01/11/2001 01/31/2001 $0 $0 $0 -  
11. 01004 Serious 19260453 B02 V 01/11/2001 01/31/2001 $450 $450 $0 -  

Investigation Summary

Investigation Nr: 171059470
Event: 07/12/2000
Burn - Electrical Fault in Switchgear

Two electricians were installing new switchgear for a new injection molding machine. At the time of the accident, they were using a Greenlee metal fish tape to pull a rope through a conduit. They were standing just outside an open switchgear cabinet, and the conduit terminated in the rear of the cabinet. The line-side bus of some existing 480-volt, 5000-ampere switchgear was exposed and energized. It was to the right of the employees, just inside the cabinet. The employees were wearing leather work gloves rather than rubber insulating gloves. In addition, they were not wearing eye protection or protective clothing. The rope caught inside the conduit when they were almost finished with the pull. The two electricians tried to free the rope by tugging on the fish tape. They had difficulty freeing the rope, so they gave one last big tug. The fish tape either broke or came free from the end of the rope and flipped into the line side of the energized switchgear, causing an electrical fault. The ensuing electric arc burned the two employees on their heads, necks, and arms. Employee #1, who was closest to the arc and in front of Employee #2, received the severest injuries. On-site emergency medical technicians treated the injured employees. The electricians were flown by helicopter to a burn center, where they were hospitalized.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, PPE, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT, SWITCHGEAR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303608095 Hospitalized injury Burn/Scald(Heat) Electricians
2 303608095 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.