Powered by GoogleTranslate

Inspection Detail

Inspection: 301986212 - Mdr Construction, Inc

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 301986212
Report ID: 0627100
Date Opened: 05/07/1998

Site Address:
Mdr Construction, Inc
Highway 49 South 15 Mile West Of
Wynne, AR 72396

Mailing Address:
621 East Baylis, Columbia, MS 39429

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 05/08/1998

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 08/31/1998


Related Activity
Type Activity Nr Safety Health
Accident 360914899
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $6,000 $0 $0 $0 $0 $6,000
Current Penalty $6,000 $0 $0 $0 $0 $6,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B01 08/06/1998 08/12/1998 $1,750 $1,750 $0 -  
2. 01002 Serious 19260951 A01 III 08/06/1998 08/12/1998 $1,750 $1,750 $0 -  
3. 01003 Serious 19260952 B02 08/06/1998 08/12/1998 $2,500 $2,500 $0 -  

Investigation Summary

Investigation Nr: 200260305
Event: 05/06/1998
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU LOAD LINE

A power line crew was installing an overhead power line in a rural area. One of the power line workers was using a winch attached to a digger-derrick positioned under the line to pull the last phase conductor of the line up to the crossarm of a utility pole. The end of the conductor somehow twisted, causing it to point in a vertical position. The conductor went beneath the insulating blanket covering a conductor on a nearby energized line and contacted the energized line. This energized the digger-derrick, electrocuting an employee leaning against it.

Keywords: DIGGER-DERRICK, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301986212 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.