Powered by GoogleTranslate

Inspection Detail

Inspection: 301341459 - Western Resources, Inc

Inspection Information - Office: Wichita Area Office

 

Inspection Nr: 301341459
Report ID: 0729710
Date Opened: 11/25/1997

Site Address:
Western Resources, Inc
1250 N. 1800 Rd
Lawrence, KS 66044

Mailing Address:
, , 00000

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/20/1998

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/05/1999


Related Activity
Type Activity Nr Safety Health
Accident 101850063
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6 1 13
Current Violations 1 3 4
Initial Penalty $30,000 $420,000 $0 $5,000 $0 $455,000
Current Penalty $0 $0 $0 $0 $200,000 $200,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 D01 05/21/1998 07/07/1998 $0 $5,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002A Other 19100137 B02 VIII 05/21/1998 06/23/1998 $0 $5,000 $0 I - Informal Settlement  
3. 01002B Other 19100137 B02 XII 05/21/1998 06/23/1998 $0 $0 $0 I - Informal Settlement  
4. 01003 Serious 19100269 A02 I 05/21/1998 07/07/1998 $0 $5,000 $0 I - Informal Settlement Citation has been deleted.
5. 01004 Serious 19100269 A02 VII 05/21/1998 07/07/1998 $0 $5,000 $0 I - Informal Settlement Citation has been deleted.
6. 01005 Serious 19100269 A03 05/21/1998 05/26/1998 $0 $5,000 $0 I - Informal Settlement Citation has been deleted.
7. 01006A Serious 19100269 D02 IIB 05/21/1998 07/07/1998 $5,000 $5,000 $0 I - Informal Settlement Citation has been deleted.
8. 01006B Serious 19100269 D02 IVB 05/21/1998 07/07/1998 $0 $0 $0 I - Informal Settlement Citation has been deleted.
9. 01006C Serious 19100269 D02 VD 05/21/1998 07/07/1998 $0 $0 $0 I - Informal Settlement Citation has been deleted.
10. 01006D Serious 19100269 D02 VIA 05/21/1998 07/07/1998 $0 $0 $0 I - Informal Settlement Citation has been deleted.
11. 01007 Unclass 19100269 L06 II 05/21/1998 07/07/1998 $5,000 $5,000 $0 I - Informal Settlement  
12. 02001 Willful 19100132 A 05/21/1998 05/26/1998 $70,000 $70,000 $0 I - Informal Settlement Citation has been deleted.
13. 02002 Willful 19100269 A02 IIC 05/21/1998 05/26/1998 $70,000 $70,000 $0 I - Informal Settlement Citation has been deleted.
14. 02003 Willful 19100269 A02 IID 05/21/1998 07/07/1998 $0 $70,000 $0 I - Informal Settlement Citation has been deleted.
15. 02004 Willful 19100269 C01 05/21/1998 05/26/1998 $70,000 $70,000 $0 I - Informal Settlement Citation has been deleted.
16. 02005 Willful 19100269 L02 05/21/1998 05/26/1998 $0 $70,000 $0 I - Informal Settlement Citation has been deleted.
17. 02006 Willful 19100269 V05 II 05/21/1998 05/26/1998 $0 $70,000 $0 I - Informal Settlement Citation has been deleted.
18. 02007A Unclass 19100132 D01 05/21/1998 07/07/1998 $0 $0 $0 -  
19. 02007B Unclass 19100132 A 05/21/1998 05/26/1998 $55,000 $0 $0 Q - National Office Adjustment  
20. 02008A Unclass 19100269 A02 I 05/21/1998 07/07/1998 $0 $0 $0 -  
21. 02008B Unclass 19100269 A02 VII 05/21/1998 07/07/1998 $0 $0 $0 -  
22. 02008C Unclass 19100269 A03 05/21/1998 05/26/1998 $0 $0 $0 -  
23. 02008D Unclass 19100269 A02 IIC 05/21/1998 05/26/1998 $70,000 $0 $0 Q - National Office Adjustment  
24. 02008E Unclass 19100269 A02 IID 05/21/1998 07/07/1998 $0 $0 $0 -  
25. 02008F Unclass 19100269 C01 05/21/1998 05/26/1998 $70,000 $0 $0 Q - National Office Adjustment  
26. 02008G Unclass 19100269 L02 05/21/1998 05/26/1998 $0 $0 $0 -  
27. 02008H Unclass 19100269 V05 II 05/21/1998 05/26/1998 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201841061
Event: 11/24/1997
BURN - ELECTRICAL FAULT IN CIRCUIT BREAKER

At 4:39 p.m. on November 24, 1997, three employees were troubleshooting a 4160-volt circuit breaker that was not closing properly. They had been working on the circuit breaker since 6:00 a.m. They had removed a fixed guard and shutter from the front of the stabs inside the circuit breaker cubicle, exposing the energized current transformers. While the employees were handling the fixed guard and shutter, it is believed that a metal rim on the shutter fell or was dropped against the current transformers, causing an electrical fault that drew 43 kiloamperes. All three employees were burned by the ensuing electric arc. One died at the scene. The other two died of their injuries within a week. (One of the fatalities was not listed on an injury line on the original form.)

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, E PTD, CIRCUIT BREAKER, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301341459 Fatality Burn/Scald(Heat) Supervisors; electricians & power transm. install.
2 301341459 Fatality Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.