Inspection Detail
Inspection: 301137550 - Mch Electric Inc
Inspection Information - Office: Oakland District Office
Site Address:
Mch Electric Inc
Arroyo Rd And Lomitas Ave
Livermore, CA 94550
Mailing Address:
31084 S Hwy 33, Tracy, CA 95376
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/20/2004
Planning Guide: Safety-Construction
Emphasis: S:Construction (Cship)
Case Closed: 06/23/2005
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 361482938 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 2 | 5 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $16,200 | $0 | $0 | $1,950 | $0 | $18,150 |
| Current Penalty | $2,475 | $0 | $0 | $685 | $0 | $3,160 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 3410001 A | 02/20/2004 | 03/24/2004 | $685 | $1,250 | $0 | 03/26/2004 | F - Formal Settlement | |
| 2. | 01002 | Other | 1509 A | 02/20/2004 | 03/24/2004 | $0 | $700 | $0 | 03/26/2004 | F - Formal Settlement | Citation has been deleted. |
| 3. | 02001 | Serious | 2940 B | 02/20/2004 | 03/24/2004 | $0 | $5,400 | $0 | 03/26/2004 | F - Formal Settlement | Citation has been deleted. |
| 4. | 03001 | Serious | 2940 C | 02/20/2004 | 03/24/2004 | $0 | $5,400 | $0 | 03/26/2004 | F - Formal Settlement | Citation has been deleted. |
| 5. | 04001 | Serious | 29400006 A01 | 02/20/2004 | 03/24/2004 | $2,475 | $5,400 | $0 | 03/26/2004 | F - Formal Settlement |
Investigation Summary
On August 22, 2003, Employee #1, a laborer, was instructed by his foreman to cut into a 3 in. thick PVC conduit so that a branch conduit could be installed. He had hand-sawed 2 in. into the conduit when he contacted an energized, 21 kilovolt conductor. The conductor shorted, causing an arc blast that was contained by the PVC conduit. Employee #1 sustained first-degree burns from the electric shock. He was transported to Valley Medical Center in Pleasanton, CA, where he was treated and released. The employer was cited for serious violations of T8CCR 2940(b), T8CCR 2940(c), and T8CCR 2940.6(a)(1).
Keywords: BURN, ELECTRIC ARC, WORK RULES, STRUCK AGAINST, CONSTRUCTION, ELECTRICAL WORK, ELECTRIC SHOCK, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 301137550 | Non Hospitalized injury | Electric Shock | Construction laborers |
Translate