Powered by GoogleTranslate

Inspection Detail

Inspection: 300964368 - Red Simpson, Inc.

Inspection Information - Office: Birmingham Area Office

 

Inspection Nr: 300964368
Report ID: 0418300
Date Opened: 05/08/1998

Site Address:
Red Simpson, Inc.
400 Nowlin Avenue
Gadsden, AL 35903

Mailing Address:
P.O. Box 23732, Harahan, LA 70183

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 07/13/1998

Emphasis:

Case Closed: 08/12/1998


Related Activity
Type Activity Nr Safety Health
Accident 101270338
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $4,250 $0 $0 $0 $0 $4,250
Current Penalty $2,125 $0 $0 $0 $0 $2,125
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 A02 IVB 07/14/1998 08/07/1998 $0 $2,125 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100269 L02 07/14/1998 07/24/1998 $2,125 $2,125 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201270501
Event: 05/08/1998
Electric Shock - Ground Fault in Crossarm Brace

A power line worker climbed a utility pole to replace a broken insulator on a 4000-volt overhead power line. The employee had rubber insulating gloves in his possession but had not yet donned them. As he was positioning himself on the pole, he simultaneously contacted the crossarm brace and pole the ground. He received an electric shock and fell from the pole. He died either from the electric shock or from injuries sustained in the fall. A 4000-volt phase conductor had been lying directly on top of the crossarm. The voltage on the metal brace was measured at 2340 volts during the investigation of the accident. The pole ground was discolored, and the adjacent wood showed burn marks where the worker had placed one of his hands.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, GROUND FAULT, EQUIPMENT GROUNDING, ELEC UTILITY WORK, ELECTRIC SHOCK, FALL, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300964368 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.