Employee Receives Burns While Testing Circuit Breaker

At approximately 9:13 a.m. on November 24, 2003, an employee, a chief engineer, was informed that the variable frequency drive for the cooling towers in the Macy's Men's store had tripped out. He and a coworker, his assistant, went to the location, opened the cover and conducted a visual inspection of the unit and checked for the possibility of a bad motor starter. The starter looked good and they found no other visible problem with the unit. Then they went out on the roof area where the disconnect switches of the cooling towers are located. They opened the cover and attempted to take them out of the circuit so they could check the variable frequency drive first. The employee reset the circuit breaker for the unit. The breaker did trip out. He opened the cover to check the line and load voltages. According to the employee, at first, he saw to it that the test meter was set correctly, then he placed the two leads from his test meter on lines #1 and #2 terminals of the incoming voltage. For an unknown reason, suddenly, the explosion occurred. The electrical tester used to test the voltage had burnt the leads. At the time of investigation, the drive still had 480-volt power. According to Sierra Electric Company, who did the testing of the circuit, the feeders to the drive were Tapped off a 400 amps current and there was no over current protection. The employee received third degree burns to his hand and face. He was hospitalized and treated at the San Francisco general Hospital.

Keywords: ELECTRIC ARC, FIRE, CIRCUIT BREAKER, ELECTRICAL FAULT, FACE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300894318 Hospitalized injury Burn/Scald(Heat) Engineers, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.