Powered by GoogleTranslate

Inspection Detail

Inspection: 300606274 - Rite Electric Company

Inspection Information - Office: Fairview Heights Area Office

 

Inspection Nr: 300606274
Report ID: 0524530
Date Opened: 02/26/1998

Site Address:
Rite Electric Company
Granite City High School
Granite City, IL 62040

Mailing Address:
2167 Lee Avenue, Granite City, IL 62040

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/01/1998

Emphasis:

Case Closed: 12/17/1998


Related Activity
Type Activity Nr Safety Health
Accident 100840206
Referral 200840221 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations
Initial Penalty $9,500 $0 $0 $0 $0 $9,500
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 05/08/1998 05/18/1998 $2,500 $2,500 $0 05/21/1998 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19260416 A01 05/08/1998 05/18/1998 $7,000 $7,000 $0 05/21/1998 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 200840320
Event: 03/24/1998
burn - electrical fault in switchboard cubicle

On February 24, 1998, during the construction of a hospital expansion, two journeyman electricians and an apprentice electrician were modifying the existing main 480-volt switchboard to add a new switchboard cubicle. The apprentice was not actively involved in the installation work and was observing from a distance. The switchboard was energized while the electricians were making the modifications. Both employees were wearing Class 1 rubber insulating gloves with leather protectors. After installing supports for the new cubicle and three Z-bar bus extensions onto the three bus bars, they lifted the new cubicle into place in the unit. An electrical fault occurred, and the ensuing electric arc burned both electricians, knocked them backwards, and ignited their clothing. Both electricians were hospitalized with second- and third-degree burns over 60 percent of their bodies. One of them died 28 days after the accident. The apprentice received minor burns on his right arm assisting the two injured electricians. (This injured employee was not listed on an injury line on the original form.)

Keywords: BURN, CLOTHING, ELECTRIC ARC, E GI IV, ELECTRICAL, SWITCHBOARD, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300606274 Fatality Burn/Scald(Heat) Electricians
2 300606274 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close