Powered by GoogleTranslate

Inspection Detail

Inspection: 300603271 - Central Illinois Public Service Company

Inspection Information - Office: Fairview Heights Area Office

 

Inspection Nr: 300603271
Report ID: 0524530
Date Opened: 10/09/1996

Site Address:
Central Illinois Public Service Company
R.R. 4, Box 260
Newton, IL 62448

Mailing Address:
, , 00000

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Complaint

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/04/1996

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/22/1998


Related Activity
Type Activity Nr Safety Health
Complaint 200826824 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $7,000 $0 $0 $0 $0 $7,000
Current Penalty $4,000 $0 $0 $0 $0 $4,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19101200 H03 III 02/13/1997 02/19/1997 $4,000 $7,000 $0 02/24/1997 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200840148
Event: 09/09/1996
ACID BURN - TANK RUPTURE CAUSED BY IMPROPER MIXING

A truck driver employed by a transportation company arrived at an electric power generation station with 3600 gallons of sodium hydroxide solution. The driver was directed to a hazardous materials off-loading point located at the station's water treatment plant. A chemist employed by the electric company met the driver at the off-loading point. The two employees had a conversation, the contents of which could not be reliably determined. After the chemist departed, the driver connected the tank trailer's transfer hose to what he apparently thought was the proper line (in violation of recognized industry practices). Unfortunately, he had connected the hose to a line for a 10,000-gallon sulfuric acid tank. When the driver transferred the sodium hydroxide solution to the sulfuric acid tank, an explosion occurred. The explosion ruptured the acid tank, and the acid severely burned the driver over 16 percent of his body.

Keywords: BURN, TANK TRUCK, SODIUM HYDROXIDE, EXPLOSIVE MIXING, EXPLOSION, SULFURIC ACID, TANK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300603271 Hospitalized injury Burn(Chemical) Truck drivers, heavy
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close