Powered by GoogleTranslate

Inspection Detail

Inspection: 300455631 - Teledyne Industries Inc

Inspection Information - Office: Tennessee Osha Nashville Office - Safety

 

Inspection Nr: 300455631
Report ID: 0454712
Date Opened: 12/03/1997

Site Address:
Teledyne Industries Inc
One Teledyne Place
La Vergne, TN 37086

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3545

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/04/1997

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/27/2000


Related Activity
Type Activity Nr Safety Health
Accident 361012297
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $15,000 $0 $0 $0 $0 $15,000
Current Penalty $7,500 $0 $0 $0 $0 $7,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100332 B01 02/04/1998 04/22/1999 $2,500 $5,000 $0 F - Formal Settlement  
2. 01002 Serious 19100333 B02 02/04/1998 03/13/1998 $2,500 $5,000 $0 F - Formal Settlement  
3. 01003A Serious 19100333 B02 I 02/04/1998 04/22/1998 $2,500 $5,000 $0 F - Formal Settlement  
4. 01003B Serious 19100333 B02 IIA 02/04/1998 04/22/1998 $0 $0 $0 F - Formal Settlement  

Investigation Summary

Investigation Nr: 170758908
Event: 12/03/1997
ELECTRIC SHOCK - CONTACT WITH ENERGIZED CONDUCTOR

An electrician working the night shift at a metal working plant was instructed to rewire the cooling fan motor on a furnace. He was to reconnect the motor supply conductors to a 480/277-volt line that serviced an adjacent furnace. The second furnace was in operation while the electrician was performing this task. Standing on a 1.8-meter ladder, the employee ran the motor supply conductors through a section of metal conduit. He then started connecting the conductors to their terminals. When he connected the first conductor to an energized terminal, the other two conductors became energized by backfeed through the load at the second furnace. He was using a screwdriver and wire strippers. He grabbed the second conductor, cut into it with the wire stripper, and was electrocuted.

Keywords: VOLTAGE BACKFEED, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300455631 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close