Inspection Information - Office: Iowa 0751910

 

Inspection Nr: 300377991
Report ID: 0751910
Date Opened: 06/26/2000

Site Address:
Hooper Corporation
16th Avenue S.W.
Cedar Rapids, IA 52404

Mailing Address:
2030 Pennsylvania Avenue, Madison, WI 53704

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/25/2000

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Fatality Catastrophe

Case Closed: 06/05/2001


Related Activity
Type Activity Nr Safety Health
Accident 361878721
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 1 1
Initial Penalty $27,000 $0 $0 $0 $0 $27,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 C01 08/08/2000 09/25/2000 $0 $4,500 $0 08/31/2000 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19260950 D01 I 08/08/2000 09/25/2000 $5,000 $4,500 $0 08/31/2000 F - Formal Settlement  
3. 01003 Serious 19260950 D01 II 08/08/2000 09/25/2000 $0 $4,500 $0 08/31/2000 F - Formal Settlement Citation has been deleted.
4. 01004 Serious 19260950 D01 III 08/08/2000 09/25/2000 $0 $4,500 $0 08/31/2000 F - Formal Settlement Citation has been deleted.
5. 01005 Serious 19260950 D01 IV 08/08/2000 09/25/2000 $0 $4,500 $0 08/31/2000 F - Formal Settlement Citation has been deleted.
6. 01006 Serious 19260954 A 08/08/2000 09/25/2000 $0 $4,500 $0 08/31/2000 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 200521714
Event: 06/23/2000
Electric Shock - Direct Contact with Energized Conductor

A journeyman power line worker was removing a pole-mounted 7200/240-volt transformer. He removed and coiled the jumper to primary-side phase conductor. He then operated what he thought was the disconnect switch for the secondary. He removed his rubber insulating gloves and placed his hands on the ungrounded primary terminal on the transformer. The switch did not control the secondary, and the primary terminal was apparently energized by backfeed through the transformer. The employee was electrocuted. He had entry and exit burns on his hands and stomach.

Keywords: VOLTAGE BACKFEED, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK, TRANSFORMER, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300377991 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.