Powered by GoogleTranslate

Inspection Detail

Inspection: 300204906 - V-1 Propane

Inspection Information - Office: Boise Area Office

 

Inspection Nr: 300204906
Report ID: 1032500
Date Opened: 07/16/1997

Site Address:
V-1 Propane
38 W. Center
Victor, ID 83455

Mailing Address:
250 S. Hwy. 33, Driggs, ID 83422

Union Status: NonUnion

SIC:5172

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/16/1997

Emphasis:

Case Closed: 08/11/1998


Related Activity
Type Activity Nr Safety Health
Accident 100230200
Referral 200230605 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $800 $0 $0 $0 $0 $800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 10/28/1997 12/16/1997 $800 $2,500 $0 11/11/1997 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200230258
Event: 07/15/1997
Two employees injured in separate propane explosions

On July 13, 1997, Employee #1 suffered second-degree burns on his hands and head when an explosion took place as he lit the pilot light on a propane water heater in the basement of a hotel. On July 15, 1997, after an investigation that did not include air testing, Employee #2 entered the basement to get information on the water heater. He did not have an intrinsically safe flashlight, and chose to use a lighter for illumination. This set off another explosion, and Employee #2 suffered second-degree burns on his hands, arms, and head. It was later determined that propane gas had been leaking from a tank buried beneath the floor. Because the propane had migrated through the soil, its odorant had faded. When the gas subsequently pooled in the basement, it had no detectable odor.

Keywords: BURN, HEAD, FLAMMABLE VAPORS, WORK RULES, AIR MONITORING, STORAGE TANK, EXPLOSION, GAS LEAK, PROPANE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300204906 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 300204906 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close