Powered by GoogleTranslate

Inspection Detail

Inspection: 300006491 - Irby Construction Co.

Inspection Information - Office: Kansas City Area Office

 

Inspection Nr: 300006491
Report ID: 0728500
Date Opened: 11/12/1997

Site Address:
Irby Construction Co.
Double N Road
Neosho, MO 39201

Mailing Address:
817 South State Street, Jackson, MS 39201

Union Status: NonUnion

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 04/08/1998

Emphasis:

Case Closed: 03/23/1999


Related Activity
Type Activity Nr Safety Health
Accident 100000454
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 1 1
Initial Penalty $21,000 $70,000 $0 $0 $0 $91,000
Current Penalty $5,000 $0 $0 $0 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260021 B02 04/08/1998 04/20/1998 $7,000 $7,000 $0 05/01/1998 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19260950 C01 04/08/1998 04/20/1998 $7,000 $7,000 $0 05/01/1998 F - Formal Settlement Citation has been deleted.
3. 01003 Serious 19260954 F 04/08/1998 04/20/1998 $7,000 $7,000 $0 05/01/1998 F - Formal Settlement Citation has been deleted.
4. 02001 Serious 19260416 A01 04/08/1998 01/22/1999 $5,000 $70,000 $0 05/01/1998 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200000453
Event: 11/11/1997
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU ARMOR ROD

A power line crew was installing all dielectric self-supporting fiber-optic cable onto structures supporting an existing 69-kilovolt overhead power line. As part of the project, the crew reinforced the existing structures and installed the fiber-optic cable. To install the cable, the crew would hang sheaves, use a pulling rope to pull the cable through the sheaves, and permanently attach the cable to the structure. The employees would reinforce the existing structures by replacing some poles, installing additional cross braces below the power line, and installing supporting braces above the crossarm. The employees worked with the power line energized some of the time and deenergized at other times. The employer relied on employee work practices to avoid violating the minimum approach distance when the line was energized. However, because of the placement of the braces and fiber-optic cable, maintaining the minimum approach distance was not possible on most structures. One of the employees was completing the task of clipping in the fiber-optic cable on a two-pole structure while the power line was energized. The employee was attaching the cable to the structure with a housing that included a rubber boot and reinforcing rods. As the employee was wrapping the rods around the cable, one of the rods got stuck. When he jerked on the 1.8-meter-long rod to free it, it passed too close to the power line, and current arced to the rod. The employee was electrocuted and set on fire by the electric arc. His coworkers conducted pole-top rescue, lowered him to the ground, and administered cardio-pulmonary resuscitation. Their efforts were to no avail as the injured employee was pronounced dead at the scene.

Keywords: ELECTRIC ARC, OVERHEAD POWER LINE, ELECTRICAL, ARMOR ROD, POWER LINE WORKER, STUCK, ELECTROCUTED, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300006491 Fatality Other Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close