Powered by GoogleTranslate

Inspection Detail

Inspection: 300004686 - Mfa Agri Service

Inspection Information - Office: Kansas City Area Office

 

Inspection Nr: 300004686
Report ID: 0728500
Date Opened: 07/11/1997

Site Address:
Mfa Agri Service
506 Boonville
Springfield, MO 65806

Mailing Address:
, , 00000

Union Status: Union

SIC:2048

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/12/1997

Emphasis:

Case Closed: 10/29/1997


Related Activity
Type Activity Nr Safety Health
Accident 100000348
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $2,250 $0 $0 $0 $0 $2,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100333 A 10/01/1997 11/14/1997 $2,250 $4,500 $0 I - Informal Settlement  
2. 01001B Serious 19100333 A02 10/01/1997 11/14/1997 $0 $0 $0 I - Informal Settlement  
3. 01001C Serious 19100333 C02 10/01/1997 11/14/1997 $0 $0 $0 I - Informal Settlement  
4. 02001 Other 19100137 B02 XII 10/01/1997 11/14/1997 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200000230
Event: 07/09/1997
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED CONDUCTOR

A supervisory maintenance electrician was tracing electrical wiring in a conduit that was 3.7 meters above the floor. The 480-volt circuit was energized while he was working. The employee was standing on the fourth step of a Louisville Ladder 1.8-meter fiberglass stepladder. He was using a Wiggins electrical tester rated at 600 volts, rubber handled wire cutters, a rubber handled screwdriver, and a roll of electrical tape. To get to the wiring, he had to reach across a metal auger that was 300 millimeters below the conduit. He had removed the covers from five electrical boxes and had pulled the conductors out of three of them. Apparently, as his left arm rested on the metal auger, his right hand contacted a bare spot on a conductor. (His tools and equipment were found atop the auger.) The employee received an electric shock and fell from the ladder, landing on the concrete floor. The injured employee was transported to a hospital where he was pronounced dead. The medical examiner ruled that the cause of death was electrocution.

Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300004686 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.